Browse > Article
http://dx.doi.org/10.5370/JEET.2007.2.3.401

Uncertainty Analysis in Potential Transformer Calibration Using a High Voltage Capacitance Bridge  

Jung, Jae-Kap (Korea Research Institute of Standards Science)
Lee, Sang-Hwa (Korea Research Institute of Standards Science)
Kang, Jeon-Hong (Korea Research Institute of Standards Science)
Kwon, Sung-Won (Korea Research Institute of Standards Science)
Kim, Myung-Soo (Korea Research Institute of Standards Science)
Publication Information
Journal of Electrical Engineering and Technology / v.2, no.3, 2007 , pp. 401-407 More about this Journal
Abstract
Precise absolute measurement of the errors in a potential transformer (PT) can be achieved using high voltage capacitance bridge (HVCB) and capacitive divider. The uncertainty in a PT measurement using the HVCB system was evaluated by considering the overall factors affecting during the calibration of a PT. The expanded uncertainties are found to be not more than $30{\times}10^{-6}$ for ratio and $30{\mu}rad$ for phase up to the primary voltage of $V_p=22kV$. For same PTs, the measured errors in KRISS (Korea Research Institute of Standards and Science) using our bridge are well coincide with those in NMIA (National Measurement Institute of Australia) and PTB (Physikalisch-Technische Bundesanstalt) within the corresponding uncertainties.
Keywords
High Voltage Capacitance Bridge; Potential Transformer; Ratio Error; Phase Displacement; Uncertainty; PT Comparator; Capacitor;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 G. Gao and D. Xu, 'Experimental Study of the Voltage Coefficient of Precise Compressed-Gas Capacitors' IEEE Trans. on Instrumentation and Measurement, vol. 42, no. 1, pp. 64-68, February 1993   DOI   ScienceOn
2 E. B. Shim, J. W. Woo and S. O. Han, 'Digital Time-Domain Simulation of Ferroresonance of Potential Transformer in the 154 kV GAS Insulated Substation' KIEE International Transactions on PE, vol. 11A-4, pp. 9-14, 2001
3 G. S. Choi, S. Y. Yoon, S. H. Baek and K. Yong, 'Power Loss Calculation of High Frequency Transformers' J. Electrical Engineering & Technology, vol. 1, no. 3, pp. 338-342, 2006   과학기술학회마을   DOI   ScienceOn
4 Tettex Instruments, 'High Quality Measuring Instruments' General Catalog, pp. 4-4, 1999
5 ZERA GmbH, 'Test equipments of instrument transformers' Instruction Manual, pp. 11, 2004
6 W. E. Anderson 'A Calibration Service for Voltage Transformers and High-Voltage Capacitors' NBS Measurement Services Special Publication, pp. 250-33, June 1988
7 G. Jones, 'The Traceable Calibration of Voltage Transformers' NPL Special Publication, 1994
8 N. L. Kusters and O. Petersons, 'A Transformer Ratio Arm Bridge for High Voltage Capacitance Measurements' IEEE Trans. Communication and Electronics, vol. 82, pp. 606-611, 1963
9 Eddy So, 'A Microprocessor-Controlled high Voltage Current Comparator Based Capacitance Bridge' IEEE Trans. on Power Delivery, vol. 5, no. 2, pp. 533-537, April 1990   DOI   ScienceOn
10 Eddy So, Hans-Georg Latzel, 'NRC-PTB Intercomparison of Voltage transformer Calibration Systems for High Voltage at 60 Hz, 50 Hz, and 16.66 Hz' IEEE Trans. on Instrumentation and Measurement, vol. 50, no. 2, pp. 419-421, April 2001   DOI   ScienceOn
11 J. K, Jung, S. W. Kwon, K. T. Kim, and M. Kim, 'A Study on Ratio Error and Phase Angle Error Caused by an External Burden in Voltage Transformer' Trans. KIEE. vol. 53C, no. 3, pp 137-142, March 2004
12 W. J. M. Moore and P. N. Miljanic, 'The current comparator', IEE Electrical Measurement Series, Vol. 4, London, United Kingdom, Peter Peregrinus Ltd., 1988