The Adequacy Analysis for Installation of High Speed Grounding Switches on the Korean 765kV Single Transmission Line  

Ahn, Sang-Pil (Korea Electrotechnology Research Institute)
Kim, Chul-Hwan (Department of Information and Communication Engineering, Sungkyunkwan University)
Park, Nam-Ok (Korea Electrotechnology Research Institute)
Ju, Hyung-Jun (Korea Electric Power Research Institute)
Shim, Eung-Bo (Korea Electric Power Research Institute)
Publication Information
Journal of Electrical Engineering and Technology / v.1, no.4, 2006 , pp. 427-434 More about this Journal
Abstract
This paper analyzes arc phenomena including the secondary arc's elongation in the Korean 765kV single transmission line (79km) between Sin-Ansung S/S and Sin-Gapyeong S/S, which will be installed in Korea in June 2006. In particular, both frequency independent and frequency dependent line models are compared to make our final decisions. As well, the significant simulation results are investigated by the EMTP program. As a result, there is no need of HSGS in the Korean 765kV single transmission line from both a practical and an economical point of view.
Keywords
EMTP; High speed grounding switches (HSGS); Secondary arc; Ultra high voltage transmission line;
Citations & Related Records
연도 인용수 순위
  • Reference
1 Laurent Dube, Users Guide to MODELS in ATP (New Version), April, 1996
2 M. Kizilcay, L. Prikler, G. Ban and P. Handl, 'Improved Secondary Arc Models based on Identification of Arc Parameters from Staged Fault Test Records', in Proc. 14th Power Systems Computation Conf., Session 24-Paper 3, June 2002
3 I. M. Dudurych, T.J. Gallagher, E. Rosolowski, 'Arc Effect on Single-Phase Reclosing Time of a UHV Power Transmission Line', IEEE Trans. Power Delivery, vol. 19, no. 2, pp. 854-860, April 2004   DOI   ScienceOn
4 S.P. Ahn, C.H. Kim, R.K. Aggarwal and A.T. Johns, 'An alternative approach to adaptive single pole autoreclosing in high voltage transmission systems based on variable dead time control', IEEE Trans. Power Systems, vol. 16, no. 4, pp. 676-686, Oct. 2001
5 C.H. Kim, S.P. Ahn, 'A Study on the Arc Modeling in Transmission Lines using EMTP', in Proc. of the Int'l Power Engineering Coni, Singapore, vol. I, pp. 52-57, May 1999
6 Canadian/American EMTP User Group, ATP Rule Book, 1995
7 A.T. Johns, R.K. Aggarwal and Y.H. Song, 'Improved Techniques for Modeling Fault Arcs on Faulted EHV Transmission Systems', lEE Proc-Gener. Transm. Distrib., vol. 141, no. 2, pp. 148-154, March 1994   DOI   ScienceOn
8 Korea Electric Power Corporation (KEPCO), 'A Study on the Protective Relaying Scheme for 765kV Power System', pp. 110-115,242-259, 1994
9 C. H. Kim and S. P. Ahn, 'The simulation of high speed grounding switches for the rapid secondary arc extinction on 765 kV transmission lines,' in Proc. of the Int'l Conf on Power Systems Transients, Hungary, pp. 173-178, June 1999
10 Korea Electric Power Corporation (KEPCO), 'Report for 765kV facilities', Jan. 2004
11 S. Goldberg, William F. Horton and D. Tziouvaras, 'A Computer Model of the Secondary Arc in Single Phase Operation of Transmission Lines', IEEE Trans. Power Delivery, vol. 4, no. 1, pp. 586-594, Jan. 1989   DOI   ScienceOn