Browse > Article
http://dx.doi.org/10.5370/JEET.2006.1.4.423

Loop Selective Direction Measurement for Distance Protection  

Steynberg, Gustav (Siemens AG PTD PA)
Koch, Geyhard (Siemens AG PTD PA)
Publication Information
Journal of Electrical Engineering and Technology / v.1, no.4, 2006 , pp. 423-426 More about this Journal
Abstract
Distance relays achieve selective tripping by measurement of all short circuit fault conditions inside set reaches. The direction of the fault, forward or reverse is commonly determined with a dedicated measurement to ensure selectivity under all conditions. For the direction decision (measurement) a number of alternatives are available. This paper describes a loop selective direction measurement and illustrates by means of a typical fault why this is superior to a non loop selective direction measurement such as that based on negative sequence quantities.
Keywords
Distance protection; Direction measurement; Polarization; Memory voltage; Faulted loop voltage; Negative sequence;
Citations & Related Records
연도 인용수 순위
  • Reference
1 G. Ziegler, Numerical Distance Protection. Erlangen:Publicis-MCD-Verl., 1999
2 Siemens, SIPROTEC 7SA522 V4.3 Manual