Browse > Article

Design and Implementation of a DSP-Based Multi-Channel Power Measurement System  

Jeon Jeong-Chay (Diagnosis Research Team, KESCO)
Oh Hun (Dept. of Electrical and Electronic Engineering, wonkwang University)
Publication Information
KIEE International Transactions on Power Engineering / v.5A, no.3, 2005 , pp. 214-220 More about this Journal
Abstract
In order to improve energy efficiency and solve power disturbances, power components measurement for both the supply and demand side of a power system must be implemented before appropriate action on the power problems can be taken. This paper presents a DSP (Digital Signal Processor)-based multi-channel (voltage 8-channel and current 10-channel) power measurement system that can simultaneously measure and analyze power components for both supply and demand. Voltage 8-channel and current 10-channel measurement is made through voltage and current sensors connected to the developed system, and power components such as reactive power, power factor and harmonics are calculated and measured by the DSP. The measured data are stored in a personal computer (PC) and a commercial program is then used for measurement data analysis and display. After voltage and current measurement accuracy revision using YOKOGAWA 2558, the developed system was tested using a programmable ac power source. The test results showed the accuracy of the developed system to be about 0.3 percent. Also, a simultaneous measurement field test of the developed system was implemented by application to the supply and demand side of the three-phase power system.
Keywords
digital signal processor (DSP); harmonics; multi-channel; power measurement;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 J. Arrillaga, N. R. Watson and S. Chen, 'Power System Quality Assessment', WILEY, January 2001
2 The report of IEEE Task Force, 'Effects of harmonics on equipment', IEEE Trans. on Power Delivery, Vol. 8, No. 2, April 1993, pp. 672-680   DOI   ScienceOn
3 Texas Instruments, 'TMS320C32 Digital Signal Processor Data sheet', http://www.ti.com , 2001
4 Dong-Jun Won, Il-Yop Chung, Joong-Moon Kim, Seon-Ju Ahn, Seung-Il Moon, Jang-Cheol Seo and Jong-Woong Choe, 'Power Quality Monitoring System with a New Distributed Monitoring Structure', KIEE Trans. on PE, Vol. 4-A, No. 4, pp. 214-220, 2004
5 Ringo P K Lee, L L Lai and Norman Tse, 'A Webbased Multi-channel Power Quality Monitoring System for a Large Network', Power System Management and Control, 17-19 April 2002 Conference Publication No. 488, pp. 112