Field Observation and Analysis of Wind-Induced Vibrations in Four-Bundled Conductor Transmission Lines  

Sohn, Hong-Kwan (Korea Electrotechnology Research Institute(KERI))
Lee, Hyung-Kwon (Korea Electrotechnology Research Institute(KERI))
Chu, Jang-Hee (Korea Intellectual Property Office (KIPO))
Lee, Dong-Il (Korea Electric Power Research Institute (KEPRI))
Lee, Eun-Woong (Dept. of Electrical Engineering, Chungnam University)
Publication Information
KIEE International Transactions on Power Engineering / v.3A, no.2, 2003 , pp. 109-114 More about this Journal
Abstract
This paper presents observations made on four-bundled conductor transmission lines concerning the behavior of conductors under the effect of natural winds. To know the wind-induced vibration status and how to control it, wind-induced vibrations have been recorded and analyzed from the real transmission lines. From the field observation and analysis results, subspan oscillation was found to be the main type of vibration. In addition, the data also revealed some common characteristics of the observation sites with high maintenance rates. The results will be used in controlling the subspan oscillations and protecting the conductors.
Keywords
Subspan Oscillation; Aeolian Vibration; Wake-Induced Oscillation; Spacer Damper; Transmission Line;
Citations & Related Records
연도 인용수 순위
  • Reference
1 R. Ikegami and C. B. Rawlins, 'Transmission Line Reference Book: Wind-induced Conductor Motion,' Electric Power Research Institute, 1979
2 C. Hardy and P. Van Dyke, 'Field Observations on Wind-Induced Conductor Motions,' Journal of Fluids and Structures, Vol. 9, pp. 43-60,1995
3 H. K. Sohn, H. K. Lee, and 1. H. Chu, 'Field Observations on a Subspan Oscillation in 4-Bundled Conductor Systems,' ICEE Jeju Conference 2002, pp.2361-2364, 2002
4 CIGRE Study Committee 22 - Working Group 11: 'Guide to Vibration Measurements on Overhead Lines,' ELECTRA, No. 163, Dec. 1995
5 KEPRI Technical Memo, TM.00PJ02.M2001.208, 'A Study on Countermeasures of Oscillations for 345kV 4-Bundles T/L, ' (in Korean), Korea Electric Power Research Institute, 2001
6 JIEE Working Group, 'Aeolian vibrations of transmission lines,' JIEE Report, No. 129, 1979