Browse > Article

Effects of Gas Injection on the Heating Performance of a Two-Stage Heat Pump Using a Twin Rotary Compressor with Refrigerant Charge Amount  

Heo, Jae-Hyeok (Graduate School of Mechanical Engineering, Korea University)
Jeong, Min-Woo (Graduate School of Mechanical Engineering, Korea University)
Jeon, Jong-Ug (Graduate School of Mechanical Engineering, Korea University)
Kim, Yong-Chan (Department of Mechanical Engineering, Korea University)
Publication Information
International Journal of Air-Conditioning and Refrigeration / v.16, no.3, 2008 , pp. 77-82 More about this Journal
Abstract
For heat pumps used in a cold region, it is very important to obtain appropriate heating capacity. Several studies using a variable speed compressor and an additional heater have been performed to enhance heating capacity at low ambient temperatures. However, for outdoor temperature conditions below $-15^{\circ}C$, it is still difficult to obtain enough heating capacity above the rated value. In recent studies, the application of gas injection technique into a two-stage heat pump yielded noticeable heating performance improvement at low temperature conditions. In this study, the heating performance of a two-stage gas injection heat pump with a rated capacity of 3.5 kW was measured and analyzed by varying refrigerant charge amount and EEV opening at the standard heating condition. The heating performance of the two-stage gas injection heat pump was compared with that of a two-stage non-injection heat pump. The heating capacity and COP of the two-stage gas injection heat pump were improved by 2-10% at the optimal charging condition over those of the two-stage non-injection heat pump.
Keywords
Gas Injection; Two-Stage Cycle; R-410A; Refrigerant Charge; Heat Pump;
Citations & Related Records
Times Cited By KSCI : 3  (Citation Analysis)
연도 인용수 순위
1 Kim, B. H., 2001, An experimental investigation on the variation of heating performance due to the refrigerant flow control in a variable-speed heat pump, Korea Journal of Air-conditioning and Refrigeration, Vol. 13, No. 8, pp. 746-756   과학기술학회마을
2 Cho, H., Ryu, C., Kim, Y., Kim, H. Y., 2005, Effects of refrigerant charge amount on the performance of a transcritical $CO_2$ heat pump, International Journal of Refrigeration, Vol. 28, pp. 1266-1273   DOI   ScienceOn
3 Ju, J. D., Bae, K. S., Hwang, Y. K., Lee, Y. Y, Jeong, G. H., Oh, S. K., 2005, An experimental study on the performance of a heat pump for the cold climate, Korea Journal of Air-conditioning and Refrigeration, Vol. 17, No. 1, pp. 39-46   과학기술학회마을
4 Ma, G., Chai, Q., 2004, Characteristics of an improved heat-pump cycle for cold regions, Applied Energy, Vol. 77, pp. 235-247   DOI   ScienceOn
5 ASHRAE Guideline 2, 1986, Engineering analysis of experimental data, Atlanta (GA), ASHRAE, USA
6 ASHRAE Standard 116, 1993, Methods of testing for seasonal efficiency of unitary air-conditioner and heat pumps, ASHRAE Standard 116, Atlanta (GA), ASHRAE, USA
7 Korean Standard C 9306, 1999, Airconditioner, Korean Standards Association, Korea
8 ANSI/AMCA 210, 1985, Laboratory methods of testing fans for rating, Arlington (VA), ANSI, USA
9 Chikahisa, T., Ichikawa, H., Murayama, T., 1996, Investigations on compact and high-performance heat pumps for cold regions, Transaction B of the Japan Society of Mechanical Engineers, Vol. 62, No. 593, pp. 340-346   DOI
10 Hwang, Y. J., 1998, A technical prospects and trends in small size heat pump, The Magazine of the Society of Air-conditioning and Refrigerating Engineers of Korea, Vol. 27, No. 2, pp. 165-175
11 Park, T. J., Lee, M. K., Jeong, J. H., Chang, K. S., 2003, Comparison of performance variation between R-22 and R-410A refrigeration systems, Korea Journal of Air-conditioning and Refrigeration, Vol. 15, No. 3, pp. 166-176
12 Choi, J., Kim, Y., Ha, J., 2001, Experimental study on superheat control of a variable speed heat pump, Korea Journal of Air-conditioning and Refrigeration, Vol. 13, No. 4, pp. 233-241   과학기술학회마을