Browse > Article
http://dx.doi.org/10.9726/kspse.2014.18.4.023

Development of High Performance Bubble Jet Loop Heat Pipe for Hot Water Floor Heating System  

Kim, Jong-Soo (Department of Refrigeration & Air-conditioning Engineering, Pukyong National University)
Kwon, Yong-Ha (Department of Refrigeration & Air-conditioning Engineering, Pukyong National University)
Kim, Jeong-Woong (Graduate school of department of Refrigeration & Air-conditioning Engineering, Pukyong National University)
Publication Information
Journal of Power System Engineering / v.18, no.4, 2014 , pp. 23-28 More about this Journal
Abstract
In order to increase the performance of conventional hot water floor heating system, the bubble jet loop heat pipe for the system was developed. This experiment was conducted under next conditions : Working fluid was R-134a, charging ratio was 50%. A temperature of hot water, room temperature and flow rate were $60^{\circ}C$, $15^{\circ}C$ and 0.5~1.5 kg/min, respectively. The experimental results, show that bubble jet loop heat pipe had a high effective thermal conductivity of $4714kW/m^{\circ}C$ and a sufficient heat flux of $73W/m^2$ to heat the floor to $35^{\circ}C$ in case of the 1.5 kg/min of flow rate. So the bubble jet loop heat pipe has a possibility for appling of the floor heating system. Additionally, the visualization of bubble jet loop heat pipe was performed to understand the operating principle. Bubbles made by the narrow gap between inner tube and outer tube of evaporating part generate pulsation at liquid surface of working fluid. The pulsation had slug flow and wavy flow. So working fluid circulates in the bubble jet loop heat pipe as two phase flow pattern. And large amount of heat is transferred by the latent heat from evaporating part to condensing part.
Keywords
Bubble jet loop heat pipe; Hot water floor heating;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 S. H. Lee, J. S. Kim, S. W. Gong and Y. B. Im, 2006, "An Experimental Study on the Performance of Floor-Heating Device Using Pulsating Heat Pipe", KSME spring annular conference, pp. 2448-2453.
2 D. K. Jeong, J. H. Woo and J. S. Kim, 2011, "A Study on Heat Transfer and Flow Characteristics of Bubble Jet Loop Heat Pipe", KSME spring annular conference, pp. 175-180.
3 C. S. Kang, M. I. Cho, Y. K. Kim, S. J. An, J. K. Seo and J. J. Lee, 2004, "A Preliminary Study on Floor Heating System that Uses Thermo Siphon Type Heat Pipe", SAREK summer annular conference, pp. 160.   과학기술학회마을
4 T. K. Lee, J. Y. Lee, M. J. Song and S. W. Kim, 2013, "The Comparison of Thermal Characteristics of New Han-ok Floor Heating for Applying Modern On-dol system", KIEAE, Vol. 13, No. 3, pp. 61-69.   과학기술학회마을   DOI   ScienceOn
5 John G. Collier and John R. Thome, 1994, "Convective Boiling and Condensation", Clarendon Press OXFORD, pp. 14-17.