An Experimental Study on the Array Design of BIPV System in Complex Facility of Downtown  

Lee, Ahn-Kee (Hanjin Heavy Industries & Construction(HHIC))
Kim, Jae-Chul (Dept. of Electrical Engineering, Soongsil University)
Choi, Og-man (Korea Land & Housing Corporation(LH))
Kang, Byoung-Wook (Dept. of Electrical Engineering, Soongsil University)
Publication Information
The Transactions of The Korean Institute of Electrical Engineers / v.67, no.3, 2018 , pp. 454-459 More about this Journal
Abstract
The BIPV system must be designed to reflect the architectural and electrical characteristics simultaneously because it replaces the role of the exterior material of the building, which makes it difficult to design the BIPV. The thin film type BIPV module has an electrical characteristic that the open voltage is higher and the short circuit current is lower than that of the crystalline type BIPV module. However, there are many differences in the design of the array, the collector distribution board, and the inverter in the system configuration since the crystal type BIPV module has the opposite feature. In this study, a crystalline BIPV module and a thinfilm BIPV module were applied to actual buildings. As a result, the elements to be considered in designing BIPV system were derived, and the architectural and electrical characteristics were mutually analyzed.
Keywords
BIPV; Thinfilm; Array; Tandem; System design;
Citations & Related Records
Times Cited By KSCI : 2  (Citation Analysis)
연도 인용수 순위
1 Yoon, J. H., Shin. W. C., Oh. M. H., and Park. J. H., "Effective BIPV Application Method for Reduction of Building Energy Consumption at High-rised Office Building," Architectural institute of Korea, Vol. 27, No. 8, pp. 333-342, 2011.
2 Lim. J. W., "development of envelop using BIPV (Building Integrated Photovoltaic)," Architectural institute of Korea, Vol. 20, No. 2, pp. 169-176, 2004.
3 Um. J. Y., Jang, H, I., Yoon. S. H., "Development of envelop using BIPV(Buil ding Integrated Photovoltaic)," Architectural institute of Korea, Vol. 29, No. 4, pp. 259-266, 2013.
4 Lee. S. H., Song. J. H., and Jung. S. H., "Convergence Technology trend of BIPV & Building Materials," The Korean Institute of Illuminating and Electrical Installation Engineers, Vol. 28, No. 1, pp. 35-42, 2014.   DOI
5 Yoon, J. H. "Architectural Considerations of BIPV System," Korea Green Building Council, Vol. 5, No. 4, pp. 23-30, 2012.
6 Yoon, J. H., Kim. J. I., Lee. K. S., and Yoo. K. J., "Development of Building Integrated PV(BIPV) module for the replacement of commercial building envelope materials," The Ecological Society of Korea, Vol. 4, No. 3, pp. 113-119, 2004.
7 Hong, W .H., Kim. D. S., "Study on the Application Possibility of BIPV System through Analysis of Electric Power Loads and Exterior Design in an Office Building," Architectural institute of Korea, Vol. 22, No. 2, pp. 191-199, 2006.
8 Lee. S. H., Song. J. H., and Jung. S. H., "Convergence Technology trend of BIPV & Building Materials," The Korean Institute of Illuminating and Electrical Installation Engineers, Vol. 28, No. 1, pp. 35-42, 2014.   DOI