Browse > Article
http://dx.doi.org/10.5370/KIEE.2015.64.9.1281

Comparison of The Attenuation Measurement Methods for Electromagnetic Partial Discharge Signal in 25.8 kV Gas Insulated Switchgear  

Goo, Sun-Geun (Korea Electric Power Corporation)
Han, Ki-Sun (Korea Electric Power Corporation)
Kwak, Joo-Sik (Korea Electric Power Corporation)
Joo, Hyung-Jun (Korea Electric Power Corporation)
Jeong, Moon-Gyu (Korea Electric Power Corporation)
Publication Information
The Transactions of The Korean Institute of Electrical Engineers / v.64, no.9, 2015 , pp. 1281-1287 More about this Journal
Abstract
We report the characteristics and differences of two types of attenuation measurement methods for electromagnetic partial discharge signal in GIS. The pulse method is to measure the attenuated waveforms in time domain and coverts them into frequency domain to get the attenuation spectra of given GIS section. This method simulates the real partial discharge signal. The frequency swept continuous wave method can obtain attenuation spectra directly so that it gives attenuation with low noise floor and simplicity. We show that both methods are effective and exchangeable because the attenuation results measured by two methods have similar trends
Keywords
GIS; UHF; sensor; partial discharge; attenuation; pulse; spectrum analyzer;
Citations & Related Records
연도 인용수 순위
  • Reference