Open-Phase Condition Detecting System for Transformer Connected Power Line in Nuclear Power Plant  

Ha, Che-Wung (Licensing Team for APR1400 DC, Advanced Reactors Development Lab. KHNP Central Research Institute)
Lee, Do-Hwan (Licensing Team for APR1400 DC, Advanced Reactors Development Lab. KHNP Central Research Institute)
Publication Information
The Transactions of The Korean Institute of Electrical Engineers / v.64, no.2, 2015 , pp. 254-259 More about this Journal
Abstract
On January 30, 2012 an auxiliary component of Byron Unit 2 was tripped on bus under voltage. The cause of the event was the failure of the C-phase insulator track for the Unit 2 station auxiliary transformer(SAT) revenue metering transformer. In addition to this event, other events have occurred at other plants resulting in an open-phase condition.[1] Therefore, Nuclear Regulatory Commission(NRC) has requested that not only nuclear power plant(NPP) operating company but also its Design Certification(DC) applicant have to prepare open-phase detecting system in their operating plants and design document. In this paper, various open-phase conditions are simulated in NPP using Electromagnetic Transient Program(EMTP) and Atpdraw, and open-phase condition detecting system is proposed for Main Transformer(MT), Unit Auxiliary Transformer(UAT) and SAT connected power line in NPP.
Keywords
Open-phase Condition; Nuclear Power Plant; Electromagnetic Transient Program; Transformer;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 Significant Event Report 2012-2, “Delayed Automatic Actuation of Safety Equipment on Loss of Offsite Power Due to Design Vulnerability”, WANO, 2012.6.
2 Amir Norouzi, “Open Phase Conditions in Transformers Analysis and Protection Algorithm”, MIPSYCON, 2013.11.
3 Dong-Yeol Shin, Donghyun Yun, HanJu Cha, “Problem Analysis by Iron Core Structure of the Transformer on Asymmetric Three Phase Lines and Prevention Measures”, Transactions of the Korean Institute of Electrical Engineers Vol. 61, No. 10, pp. 1536∼1541   DOI   ScienceOn
4 Laszlo Prikler, Hans Krisian Hoidalen, “ATPDRAW Users’ Manual”, SNITEF, 2002.8.
5 M. Horning, J. Kelly, S. Myers, R. Stebbins, “Transformer Maintenance Guide”, SDMyers, 2004.
6 Bong-Hee Kim, “Power System Analysis and Coordination of Industrial Power System”, KIDARI, 2010.4.
7 R. Arritt. ect, “Development and Analysis fo an Open-Phase Detection Scheme”, EPRI, 2012.9.
8 Bulletin 2012-01, “Design Vulnerability in Electric Power System”, NRC, 2012.7.