Browse > Article
http://dx.doi.org/10.5370/KIEE.2014.63.5.629

Effects Analysis of Partial Discharge Signal Propagation Characteristics in Underground Transmission Cables Using EMTP  

Jung, Chae-Kyun (KEPCO Research Institute)
Jang, Tai-In (KEPCO Research Institute)
Publication Information
The Transactions of The Korean Institute of Electrical Engineers / v.63, no.5, 2014 , pp. 629-635 More about this Journal
Abstract
This paper describes propagation characteristics obtained by considering semiconducting screen and cross-bonding in underground transmission cables. The semiconducting screen of power cable has effect on propagation characteristics including attenuation, velocity and surge impedance. However, it is very difficult to apply the semiconduction screen for EMTP model because of the number of conductors limitation. Therefore, CIGRE WG 21-05 proposed advanced insulation structure and analysis technique of simplified approach including inner and outer semiconducting screen. In this paper, the various propagation characteristics analyse using this structure and technique for 154kV XLPE $2000mm^2$ cable. The frequency independent model of EMTP CABLE PARAMETER is used for just pattern analysis of propagation characteristics. For exact data analysis, the frequency dependent model of J-marti is used for EMTP modeling. From these result, various propagation characteristics of 154kV XLPE $2000mm^2$ cable according to semi conducting screen consideration, frequency range, cable length and pulse width are analysed. In addition, in this paper, the effects of cross-bonding are also variously discussed according to cross-bonding methods, direct connection and impedance of lead cable.
Keywords
Cross-bonding; EMTP; Propagation characteristics; Semiconducting screen; Underground transmission cable;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 Mustafa Kizilcay, "Modelling of a 400kV XLPE cable by taking into consideration the semi-conducting layer of core", 2001 EEUG Meeting Proceedings
2 Bjorn Gustavsen, "Panel on Data for Modeling System Transients-Insulated Cables", IEEE Power Engineering Society Winter Meeting Proceedings, Vo1. 2, 2001
3 Bjorn Gustavsen, "The effect of lossy insulation (paper-oil) and semiconductive layers on wave propagation in cables", CIGRE WG 21-05, SINTEF Energy Research
4 G. Mugula, R. Eriksson, "High Frequency Characteristics of a Shileded Medium Voltage XLPE Cable" Conference on Elecgtrical and Dielectric Phenomena, 2001 Annual Report
5 Chae-Kyun Jung,-Beom Lee, Jeong-Tae Kim, "Analysis of Frequency Response Characteristic considering Semiconducting Screen in Underground Distribution Cables", The Transactions of the Korean Institute of Electrical Engineers Vol. 61, No. 8, 2012   과학기술학회마을   DOI   ScienceOn
6 C. K. Jung, J. W. Kang, H. S. Park. J. W. Park, T. I. Jang, D. I. Lee, "Pattern Analysis for Underground Cable Fault Location Through TDR Tests", 2011 The Korean Institute of Electrical Engineers Spring Annual Conference Proceedings, 2011.
7 C. Y. Ahn, J. B. Lee, C. K. Jung, "Analysis Evaluation of PD Considering Cross-Bonding in Underground Power Cable System", 2012 The Korean Institute of Electrical Engineers Summer Annual Conference Proceedings, 2012. 7
8 IEEJ, ""Surge Phenomena of Underground Cable Systems"", Technical Report of IEEJ, Apr. 1991.