Browse > Article
http://dx.doi.org/10.5370/KIEE.2014.63.4.589

Development of Automatic Evaluation Equipment for Burden of Instrument Transformer using Resistor Simulator  

Lee, Young Seob (Dept. of Metrology, UST)
Jung, Jae Kap (Dept. of Electricity and Magnetism, KRISS)
Publication Information
The Transactions of The Korean Institute of Electrical Engineers / v.63, no.4, 2014 , pp. 589-595 More about this Journal
Abstract
The error of instrument transformers is measured by connecting the external burden with the secondary terminal of the instrument transformers. Because the error of transformer is affected by the apparent power and power factor of the external burden, an accurate measurement of burden is important for transformer evaluation. We have developed the burden evaluation equipment for both potential transformer and current transformer by employing the series resistor in the range of $20m{\Omega}{\sim}5{\Omega}$ and the parallel resistor in the range of $1M{\Omega}{\sim}500{\Omega}$, respectively, together with visual basic program. We could reduce testing time more than 5 times by employing method developed in this study, compared with that developed in past. This method shows more better reliability by analyzing the evaluation results and fitting graphs of burden measurements. The test results of the developed system is compared with those obtained in the power meter analyzer to verify the validity.
Keywords
Current transformer; Potential transformer; Burden; Apparent power; Power factor;
Citations & Related Records
Times Cited By KSCI : 4  (Citation Analysis)
연도 인용수 순위
1 KSA, "Instrument transformers for testing purpose and used with general instrument", KS C 1706, 1982.
2 J. L. Settles, W. R. Farber, and E. E. Connor, "The analytical and graphical determination of complete potential transformer characteristics" IEEE Trans. Power Apparatus and Systems, vol. 79, No. 51, pp.1213-1218, 1961.
3 William E. Anderson "A Calibration Service for Voltage Transformers and High-Voltage Capacitors" NBS Measurement Services Special Publication 250-33, 1988.
4 Jae Kap Jung, Sung Won Kwon, Kyu Tae Kim, Myungsoo Kim, "A Study on Ratio Error and Phase Angle Error Caused by an External Burden in Voltage Transformer" KIEE, vol. 53C, No. 3, pp.137-142, 2004.   과학기술학회마을
5 P. J. Betts, "Calculated Temperature Coefficients of Transformers" National Measurement Laboratory Technical Paper No 4, pp. 1-13, 1977
6 Jae Kap Jung, Sung Won Kwon, Sang Hwa Lee, Young Tae Park, "A Study on Usefulness Verification Technique of the Measurement System by the Difference Between Caculated and Experimental Values of Ratio Error/phase Annie Error in Current Transformer", KIEE, vol. 53C No. 4, pp 213-217, 2004   과학기술학회마을
7 Jae Kap Jung, Sang Hwa Lee, Jeon Hong Kang, Myungsoo Kim, "On-Site Calibration Technology of Burden using Voltage Transformer Comparator", KIEE, vol. 54C, No. 11 , pp 503-507, 2005   과학기술학회마을
8 Jae Kap Jung, Sang Hwa Lee, Jeon Hong Kang, Myungsoo Kim, "Evaluation Technique of Burden for Current Transformer using Current Transformer Comparator and Precise Shunt Resistor", KIEE, vol. 55C, No. 5, pp 250-256, 2006   과학기술학회마을