UHF Sensor Location Optimization for Partial Discharge Signals Detection Method  

Choi, Mun-Gyu (Dept of Transmission Diagnosis Team, KEPCO)
Cha, Hanju (Dept of Electrical Engineering, Chungnam National University)
Publication Information
The Transactions of The Korean Institute of Electrical Engineers / v.63, no.3, 2014 , pp. 409-413 More about this Journal
Abstract
GIS partial discharge that occurred in the UHF band signal is effectively detected by the method to IEC60270 5pc the apparent minimum discharge can be detected over the GIS arrangement of the sensor interior and exterior of the UHF in accordance with the optimized position signal by considering the damping ratio is selected so that the signals can be obtained to be mounted. 362kV, 800kV GIS is installed on the internal and external sensors are UHF band signal attenuation is set by measuring the reference value, but the operation, 170kV case 362kV, 800kV on the basis of the measurement data and to be installed and operated. When 170kV per 1Bay by installing the built-in sensor 1 for detecting a partial discharge signal, But, GIS signal attenuation is large in the case of an internal partial discharge signal is not detected in some cases. Where the attenuation is great UHF signal of the sensor by increasing the quantity of partial discharge signals were acquired to allow relocation. The greater the spacing between the sensor and the sensor is applied simplifies the installation and reduces the cost in terms of maintenance of appropriate optimal position is calculated to detect the partial discharge signal is needed. Thus 170kV GIS signal power attenuation of a partial discharge by measuring the UHF sensor, and by relocating the proper position is calculated in accordance with the sensor signal decay rate and minimize the error of omission in detecting a partial discharge signal was optimized.
Keywords
UHF; Partial discharge; Network analyzer; Sensor;
Citations & Related Records
연도 인용수 순위
  • Reference
1 Jin-yeol Yoon, Gi-jun Park, and Sun-geun Goo, "GIS UHF partial discharge signal for the prevention of failure analysis technology research", the Korea Electric Power Corporation, 2005. 3.
2 Jin-yeol Yoon, Gi-jun Park, and Sun-geun Goo, "Partial Discharge Detection of GIS Technology Research (Final Report), 2002. 08.
3 Sun-geun Goo, Gi-jun Park, and Jin-yeol Yoon, "A Novel Sensitivity Verification Method for the UHF Partial Discharge Detection System in Gas Insulated Switchgear (GIS)", 2001. 8.
4 "Application of Combined PD Sensor for GIS PD Detection and Condition Monitoring", 2008. International Conference on Condition Monitoring and Diagnosis, Beijing, China, April, 2008.
5 Jin-yeol Yoon, Gi-jun Park, and Sun-geun Goo, "GIS for failure prevention technology research UHF partial discharge signal analysis," 2004. 8.
6 Jin-yeol Yoon, Gi-jun Park, and Sun-geun Goo, "GIS partial discharge diagnosis Fact Sheet", the Korea Electric Power Corporation, 2008. 8.
7 Sun-geun Goo et al. "Novel Calibration Method of UHF Partial Discharge Sensor for GIS", Proc. of ICEE 2002, Jeju, 2002.
8 "Transmission equipment diagnosis experts group", the Korea Electric Power Corporation, 2011.
9 "Power Office Total Information System", the Korea Electric Power Corporation, 2013.