Browse > Article
http://dx.doi.org/10.5370/KIEE.2014.63.3.367

Effects of Freshwater Flooding on the Properties of the Accelerated Thermally Aged CSPE  

Kang, Myeong-Gyun (Dept. of Electrical Engineering, Wonkwang University)
Lee, Jung-Hoon (Dept. of Electrical Engineering, Wonkwang University)
Lee, Seung-Hoon (Dept. of Electrical Engineering, Wonkwang University)
Jeon, Jun-Soo (Dept. of Electrical Engineering, Wonkwang University)
Kim, In-Yong (Expert Group Instrumentation & Electric Control Department, Korea Institute of Nuclear Safety)
Shin, Yong-Deok (Dept. of Electrical Engineering, Wonkwang University)
Publication Information
The Transactions of The Korean Institute of Electrical Engineers / v.63, no.3, 2014 , pp. 367-370 More about this Journal
Abstract
The accelerated thermal aging of a CSPE were carried out for 0, 80.82, 161.63 days at $100^{\circ}C$, which are equal to 0, 40 and 80 years, respectively. The volume electrical resistivities of the non-accelerated thermally aged CSPE and the accelerated thermally aged CSPE for 40y and 80y were $9.620{\times}10^{12}{\sim}1.246{\times}10^{13}{\Omega}{\cdot}cm$, $5.066{\times}10^{12}{\sim}7.576{\times}10^{12}{\Omega}{\cdot}cm$ and $7.195{\times}10^{12}{\sim}9.208{\times}10^{12}{\Omega}{\cdot}cm$ at room temperature, respectively. The dielectric constant of the non-accelerated thermally aged CSPE and the accelerated thermally aged CSPE for 40y and 80y were 3.355~4.030, 2.996~3.963 and 3.020~4.776 at room temperature, respectively. After seawater and freshwater flooding, the volume electrical resistivity of the CSPE trend slightly upward according to drying day at room temperature. After seawater flooding, the dielectric constant of the accelerated thermally aged CSPE were not measured. After seawater flooding, bright open pores of the accelerated thermally aged CSPE were partly transferred to dark close pores due to salinity. After freshwater flooding, dark close pores of the accelerated thermally aged CSPE were partly transferred to bright open pores because salinity of them is decreased. An insulation property of a cable in NPPs was decreased because of the seawater flooding, and an insulation property of them was recovered through the freshwater flooding. As a result, it is considered that an insulation property of a contaminated cable through Tsunami can be recovered if it is cleaned quickly.
Keywords
Accelerated thermal aging CSPE; Volume electrical resistivities; Seawater and freshwater flooding; Dielectric constant;
Citations & Related Records
연도 인용수 순위
  • Reference
1 Korea Institute of Nuclear Safety, KINS/RR-111, "Power Plant Cable Condition Monitoring method and Life Evaluation", 2002.
2 I. Y. Kim, C. S. Goo, J. H. Lee, B. S. Jin, M. K. Kang, Y. D. Shin "Effects of Seawater Flooding on the Properties of CSPE", KF012, ICAPP 2013.
3 C. S. Goo and S. P. Ahn, "Condition Monitoring of the Safety Related Cable in Nuclear Power Plant", KIEE Summer Conference, 2001.
4 US NRC NUREG/CR-7000, "Essential Elements of an Electric Cable Condition Monitoring Program", Brookhaven National Laboratory, Upton, NY, 2010.
5 Accident of Fukushima NPPs in Japan: Outcomes and impact and lessons learned (Interim Report), Korea Advanced Institute of Science and Technology, Department of Nuclear and Quantum Engineering, 2011