Browse > Article
http://dx.doi.org/10.5370/KIEE.2014.63.10.1347

Modeling and Experiment of 50kW Diesel Generator in Grid-connected Mode  

Lee, Wujong (Dept. of Electrical Engineering, Chungnam National University)
Lee, Hak Ju (Korea Electric Power Research Institute)
Chag, Hanju (Dept. of Electrical Engineering, Chungnam National University)
Publication Information
The Transactions of The Korean Institute of Electrical Engineers / v.63, no.10, 2014 , pp. 1347-1353 More about this Journal
Abstract
This paper researches a modeling and experiment of 50kW diesel generator in grid-connected mode. The output of diesel generator can be calculated by the phase difference between voltage and current as well as the diesel generator parameter such as mutual impedance, field current and rotor angle. Considering the different d-q frame impedance, the output of diesel generator is analyzed for equation and verified by simulation. The diesel generator modeled by considering the time delay for actuator, diesel engine and exciter. The controller of diesel generator is divided into governor and exciter. The governor consists of speed controller and active power controller, where speed controller maintains frequency as 60Hz and active power tracks active power reference. On the other hand, the exciter consists of voltage controller and reactive power controller, where voltage controller controls $380V_{LL}$ and reactive power is controlled as zero. When the active power reference is changed as 0.1pu in the grid connected mode, the active power takes 10 seconds to reach the steady state and the reactive power is maintains as zero. The 50kW diesel generator is tested and experiment results are well matched with the simulation results.
Keywords
Grid-connected mode; Diesel generator; Governor modeling; Exciter modeling;
Citations & Related Records
Times Cited By KSCI : 3  (Citation Analysis)
연도 인용수 순위
1 Sang-Seok Han, Hoo-sek Han, Chang-Goo Lee, "A Study on the Controller Developmetn Depending Load Variation of a Diesel Generator for Power System Connection of Distributed-source", Journal of the Korean Institute of Illuminating and Electical Installation Engineers, Vol.22, No.5, pp 53-57, May, 2008.   과학기술학회마을   DOI   ScienceOn
2 J.H. Park, K.H. Choi, S.G. Lee, "Analysis and Evaluation Study on Diesel Generator Engine Operation Signature", Journal of the Korean Society for Power System Engineering, Vol.13, No.5, pp 82-88, Oct, 2009.   과학기술학회마을
3 J.H. Park, K.H. Choi, S.G. Lee, "Analysis and Evaluation Study on Diesel Generator Engine Operation Signature", Journal of the Korean Society for Power System Engineering, Vol.13, No.5, pp 82-88, Oct, 2009.   과학기술학회마을
4 Prabha Kunder, "Power System Stability and Control", Elecrtric Power Research Institute.
5 S. Roy, O.P. Malik and G.S. Hope, "An Adaptive Control Scheme for Speed Control of Diesel Driven Power-Plants", IEEE Transactions on Energy Conversion, Vol.6, No.4, December, 1991.
6 G.S. Stavrakakis, G.N. Kariniotakis, "A Generals Simulation Algorithm or The Accurate Assessment of Isolated Diesel-Wind Turbines Systems Interaction. Part I: A General Multimachine Power System Model", IEEE Transactions on Energy Conversion, Vol.10, No.3, September, 1995.
7 "IEEE Recommended Practice for Excitation System Models for Power System Stability Sudies", IEEE Standard, 1992.
8 Ahmad Darabi, Colin Tindall, and Stuart Ferguson, "Finite-Element Time-Step Coupled Generator, Load, AVR, and Brushless Exciter Modeling" IEEE Trans. on Energy Conversion, Vol.19, No.2, June 2004.
9 A. Elmitwally, Mohamed Rashed, "Flexible Operation Strategy for an Isolated PV-Diesel Microgrid Without Energy Storage", IEEE Transaction on Energy Conversion, Vol.26, No.1, March, 2011.
10 S. Mishra, D. Ramsasubramanianm and P.C. Sekhar, "A Seamless Control Methodology for a Grid Connected and Isolated PV-Diesel Microgrid", IEEE Trans. on Power System, Vol.28, No.4, November, 2013.