Browse > Article
http://dx.doi.org/10.5370/KIEE.2013.62.7.1033

Analysis of Transient Characteristics of a SFCL Applied Into Third-winding Transformer in a Single Line-to-ground Fault  

Choi, Hye-Won (Dept. of Electrical Engineering, Chosun University)
Choi, Hyo-Sang (Dept. of Electrical Engineering, Chosun University)
Jung, Byung-Ik (Dept. of Electrical Engineering, Chosun University)
Publication Information
The Transactions of The Korean Institute of Electrical Engineers / v.62, no.7, 2013 , pp. 1033-1037 More about this Journal
Abstract
Coercion transformer is commonly used in the electrical grid which in three phase of distribution system. The accident of the electrical grid is divided into a single, a double, a third line-to-ground faults and a double, a third line-to-line faults. A single line-to-ground fault accounts for nearly 75[%] among them. In this research, when a Superconducting Fault Current Limiters (SFCL) was applied to the three phase power system, operation in a single line-to-ground fault and limiting characteristics of fault current according to turns ratio of third winding were analyzed. When a single line-to-ground fault happened, secondary winding's circuit was open. Then third winding's circuit with a SFCL was closed. So fault current was limited by diverted circuit. At this time, we could find out that size of the limited fault current could be changed according to third winding rate. We confirmed that limiting operation of the fault current was carried out within one-period. These results will be utilized in adjusting the size of the SFCL.
Keywords
Third-winding; SCR; SFCL; Superconducting element; Line-to-ground fault;
Citations & Related Records
연도 인용수 순위
  • Reference
1 T. Hara, T. Okuma, and T. Yamamoto, D. Ito K. Tasaki, K. Tsurunaga, "Development of a new 6.6kV/1500A class superconducting fault current limiter for electric power system," IEEE Trans, Appl. Power Delivery. vol. 8, no. 1, pp. 188-198, 1993.
2 H. S. Choi, O. B. Hyun, and H. R. Kim, "Quench characteristics of resistive superconducting fault current limiters based on YBCO films," Physica C, vol. 351, pp. 415-420, 2001.   DOI   ScienceOn
3 H. R. Kim, H. S. Choi, and H. R. Lim, I. S. Kim, O. B. Hyun, "Initial quench development in uniform Au/Y-Ba-Cu-O thin films," IEEE Trans, Appl. Superconduct, vol. 11, pp. 2414-2417, 2001.   DOI   ScienceOn
4 H. S. Choi, O. B. Hyun, and H. R. Kim, K. B. Park, "Switching properties of hybrid type superconducting fault current limiter using YBCO stripes," IEEE Trans, Appl. Superconduct, vol. 12, pp. 1833-1838, 2002.   DOI   ScienceOn
5 H. R. Kim, S. W. Yim, and S. Y. Oh, O. B. Hyun, "Recovery in superconducting fault current limiters at low applied voltages," IEEE Trans. Appl. Superconduct, vol. 18, no. 2, pp. 656-659, 2008.   DOI   ScienceOn
6 J. S. Kim, S. H. Lim, and J. C. Kim, "Study on protective coordination of a flux-lock type SFCL with over-current relay," IEEE Trans. Appl. Superconduct, vol. 20, no. 3, pp. 1159-1163, 2010.   DOI   ScienceOn
7 S. G. Choi, H. S. Choi, and Y. S. Cho, B. I. Jung, K. H. Ha, H. M. Park, "Characteristics of transformer-type superconducting fault current limiter depending on reclosing in changing the number of turns of secondary winding," Physica C, vol. 471, pp.1332-1336, 2011.   DOI   ScienceOn
8 S. W. Yim, S. D. Yu, and H. R. Kim, M. J. Kim, C. R. Park, S. E. Yang, W. S. Kim, O. B. Hyun, J. Sim, K. B. Park, I. S. Oh, "construction of testing facilities and verifying tests of a 22.9kV/630A class superconducting fault current limiter", Physica C, vol. 470, pp. 1611-1614, 2010.   DOI   ScienceOn