Browse > Article
http://dx.doi.org/10.5370/KIEE.2013.62.6.881

Implementation of Prediction Program for Deterioration Judgment on Substation Power Systems in Urban Railway  

Jung, Ho-Sung (High-speed Railroad Infrastructure Systems Research Team, Korea Railroad Research Institute)
Park, Young (High-speed Railroad Infrastructure Systems Research Team, Korea Railroad Research Institute)
Kang, Hyun-Il (Dept. of Electrical Engineering, Hanbat National University)
Publication Information
The Transactions of The Korean Institute of Electrical Engineers / v.62, no.6, 2013 , pp. 881-885 More about this Journal
Abstract
In this paper, we present a deterioration judgment model of urban rail power equipment using driving history, the frequency and number of failures. In addition, we have developed a deterioration judgment program based on the derived failure rate. A deterioration judgment model of power equipments on metro system was designed to establish how much environmental factors, such as thermal cycling, humidity, overvoltage and partial discharge. The deterioration rate of the transformers followed the Arrhenius log life versus reciprocal Kelvin temperature (hotspot temperature) relation. The deterioration judgment program is linked to the online condition monitoring system of urban railway system. The deterioration judgment program is based on the user interface it is possible to apply immediately to the urban rail power equipment.
Keywords
Preventive maintenance; Deterioration evaluation model; Arrhenius;
Citations & Related Records
Times Cited By KSCI : 3  (Citation Analysis)
연도 인용수 순위
1 Y. Park, H. S. Jung, S.K. Ryu, S. Y. Eo, J. M Kim, Y. S. Kim, "Analysis and Relations of Operating Authority Design Requirements for Power Facility Monitoring System in Urban Railways", KIEE Spring Conference 2009, p. 3, 2009. 10.
2 D.Z. Lee, J.C. Lee, J.T. Sim, S.Y. Oeu a.nd D.S. Kang, "Development of the On-line PD Diagnosis Device for Mold Transformers", 2007. ICSD '07. IEEE International Conf. on Solid Dielectrics, pp.593-595, 2007. 7.
3 K.T. Muthanna, A. Sarkar, K. Das, and K. Waldner, "Transformer Insulation Life Assessment", IEEE Transactions on Power Delivery, vol 21, pp. 150-156, 2006. 1.   DOI   ScienceOn
4 S.B. Pandey and C. Lin, "Estimation for a Life Model of Transformer Insulation Under Combined Electrical & Thermal Stress", IEEE Transactions on Reliability, vol 41, no. 3, pp. 466-468, 1992. 9.   DOI   ScienceOn
5 IEEE Std C57.100-1999, "IEEE Standard Test Procedure for Thermal Evaluation of Liquid-Immersed Distribution and Power Transformer", 1999.
6 D. H. Lee, M. J. Chai, M. S. Chang, S. W. Chang, K. D. Kwack, "Lifetime Estimation of a Rectifier Diode", 2007 Autumn Conference of The Korea Society of Mechanical Engineers, pp. 7-12, 2007. 10.
7 "Life assessment of electrical and electronic parts", Japanese Standard Association, 1989.
8 J. Y. Seo, H. S. Shin,, S. H. Lee, J. C. Kim, "Low Voltage Circuit Breaker Life Time Prediction of Aging Analysis", KIIEE Annual Spring Conference 2010, pp. 300-301, 2010. 5.
9 "A reliability study for long-term used power substation , The Japan Electrical Manufacturers Association, 1999.
10 H. S. Jung, Y, Park, H. E. Na, S. H. Jang, "Performance Evaluation of SHF Sensor for Partial Discharge Signal Detection on DC Rectifier" The Korean Institute of Electrical Engineers, Vol. 61, No. 7, pp. 1056-1060, 2012.   과학기술학회마을   DOI   ScienceOn
11 T. K. An, J. R. Shin, W. D. Lee, M. H. Kim, "Intelligent Surveillance System for Urban Transit using Context-aware technology", 2007 CICS, pp. 399-400, 2007. 10.
12 "Lifetime Estimation for molded transformer of coil", KERI research report, 2010.
13 H. G. Lim, B. D. Lee, T, D, Kim, S. H. Jang, "Urban Rail Power Facilities on-site Implementation of an Integrated System Diagnosis", 2011 Autumn Conference of The Korea Society for Railway, pp. 2015-2020, 2011. 10.
14 Y. Park, H. S. Jung, C. Park, S. H. Jang, "Implementation of a Condition Monitoring System for Mold Transformers in DC Substations", The Korean Institute of Electrical Engineers, Vol .60, No. 9, pp. 1788-1794, 2011.   과학기술학회마을   DOI   ScienceOn
15 J. Lee, G. S. Choi, E. S. Lee, "A study on the live line diagnostic technique of cast resin transformer by the partial discharge detection", 1999 KIEE annual autumn conference, pp. 1048-1050, 1999. 11.
16 M. K. Kim, H. G. Lee, J. Y. Jeong, I. S. Kim, "A Study on the lifetime Expectation of Dry type", KIEE Summer Conference 2005, pp. 2106-2108, 2005. 7.
17 C. Y. Park, E. W. Park, J. S. Choi, G. S. Kil, "A Study on PD Detection Methods for Cast-resin Dry-type Transformers", Journal of the Korean institute of electronic material engineers, pp. 789-791, 2009. 9.   과학기술학회마을   DOI   ScienceOn