Browse > Article
http://dx.doi.org/10.5370/KIEE.2013.62.10.1458

A Study on Real Time Catenary Impedance Estimation Technique using the Synchronized Measuring Data between Substation and Train  

Jung, Hosung (Korea Railroad Research Institute)
Publication Information
The Transactions of The Korean Institute of Electrical Engineers / v.62, no.10, 2013 , pp. 1458-1464 More about this Journal
Abstract
This paper proposed a new real time catenary impedance estimation technique using synchronized power data from the measured data of operating vehicle and substation for catenary protective relay and fault locator setting. This paper presented estimation equation of catenary impedance using synchronized power data between substation and vehicle of AT feeding system for the performance verification of the proposed technique. Also AC feeding system is modeled through power analysis program and performance was verified through simulation according to various load changes. We verified that average 2.38%(distance equivalent 23.8 m) error appeared between the proposed estimation equation of catenary impedance and power analysis program simulation output in no connection double track system between up track and down track. Furthermore, We confirmed that estimation error is bigger depending on the increasing the distance from substation and vehicle impedance using only using vehicle current when calculating vehicle impedance in connection double track system between up track and down track. But, We confirmed that the proposed technique estimated accurately catenary impedance regardless of vehicle impedance and distance from substation.
Keywords
AT feeding system; AT power simulation; Real time catenary impedance estimation; Synchronized measuring power data;
Citations & Related Records
Times Cited By KSCI : 2  (Citation Analysis)
연도 인용수 순위
1 Hanmin Lee, "A Reduced Equivalent Line Constant of the Catenary System", The Transactions of the Korean Institute of Electrical Engineers, Vol.53A, No.8, pp.421-431, 2004.8.   과학기술학회마을
2 Oh, K.H., "Measurement method for catenary line constant," The Korean Society for Railway, Vol. 9, No. 6, pp.620-627, 2006
3 Minkyu Kim, "A Study on the Impedance Calculation by using Equivalent Model in Catenary System", Journal of the Korea Society for Railway, 3(2), pp. 46-53, 2010.6   과학기술학회마을
4 Myungsoo Jun, "Trolley line impedance detector and Method for locating fault distance", 1020080026712, 2008.03
5 Hosung Jung, "A Study on Fault Location Estimation Technique Using the distribution Ratio of Catenary Current in AC Feeding System", Journal of the Korea Society for Railway, 14(5), pp. 404-410, 2011.10   과학기술학회마을   DOI   ScienceOn
6 Korea High Speed Rail Construction Authority, "Protection Relay Setting of Substation in Korea High Speed line test section.", 1999.10
7 Hosung Jung, "A study on relay setting for AT feeding system protection using PSCAD/EMTDC", ICEE 2005, pp.A76-A76, 2005
8 Korea Railroad Research Institute, "A Study on the Overhead Contact-line Constant and Optimal Strategy of Protection Circuit in the Electrical Railway Substation", Korea Railroad Research Institute, 1998
9 Tevfik Sezi, Frank E. Menter, "Protection Scheme for a New AC Railway Traction Power System", IEEE Transmission and Distribution Conference vol 1, pp388-393, 1999
10 Hosung Jung, Young Park, Moonseob Han, Hyenjune Park, "High Impedance fault detection Technique for the reliable power feeding in AT railway system", the Second International Conference on Engineering Failure Analysis, 2006