Browse > Article
http://dx.doi.org/10.5370/KIEE.2010.59.8.1347

An Adaptive Reclosing Algorithm to Discriminate between Permanent Fault and Transient Fault using THD of Voltage Waveform  

Lee, Chul-Moon (성균관대 전자전기컴퓨터공학과)
Kim, Chul-Hwan (성균관대 정보통신공학부)
Publication Information
The Transactions of The Korean Institute of Electrical Engineers / v.59, no.8, 2010 , pp. 1347-1352 More about this Journal
Abstract
This paper presents a new adaptive single-phase auto reclosure (SPAR) algorithm to discriminate between a permanent fault and a transient fault and to minimize a protection dead time. The algorithm precisely detects the extinction of the secondary arc, based on THD's profiles on the faulted phase voltage waveform. The EMTP/ATPDraw program was used to simulate the single phase grounding fault for evaluating the proposed algorithm. And the simulation results show that the proposed algorithm is performing well.
Keywords
SPAR; Adaptive reclosing; THD; Permanent fault; Transient fault;
Citations & Related Records

Times Cited By SCOPUS : 0
연도 인용수 순위
  • Reference
1 "Single phase tripping and auto reclosing of transmission lines-IEEE Committee Report," IEEE Trans. Power Delivery, Vol. 7, pp. 182-192, Jan. 1992.   DOI   ScienceOn
2 Zoran M. Radojevic, Joong-Rin Shin, "New Digital Algorithm for Adaptive Reclosing Based on the Calculation of the Faulted Phase Voltage Total Harmonic Distortion Factor," IEEE Trans. Power Delivery, Vol. 22, pp. 37-41, Jan. 2007.   DOI
3 A. A. Montanari, M. C. Tavares, C. M. Portela, "Adaptative single phase autoreclosing based on secondary arc voltage harmonic signature," International Conference on Power Systems Transients, Kyoto, Japan, Jun. 2009.
4 M. E. Golshan and N. Golbon, "Detecting secondary arc extinction time by analyzing low frequency components of faulted phase voltage or sound phase current waveforms," Electrical Engineering (Archiv fur Elektrotechnik), Vol. 88, pp. 141-148, Jan. 2006.   DOI   ScienceOn
5 Saul Goldberg, William F. Horton, Demetrios Tziouvara, "A Computer Model of the Secondary Arc in Single Phase Operation of Transmission Lines," IEEE Transactions on Power Delivery, Vol. 4, No. 1, pp. 586-595, Jan. 1989.   DOI
6 IEEE Std. C37.104-2002
7 V.V. Terzija, H-J. Koglin, "Long Arc in Free Air: Testing, Modelling, ,and Parameter Estimation: Part I," ICHQP, Vol 2, pp. 404-409, Sep. 2000.