Browse > Article
http://dx.doi.org/10.5370/KIEE.2010.59.3.506

Vulnerability Evaluation for Monitoring Wide Area Outage in Transmission Systems  

Kim, Jin-Hwan (명지대 공대 전기공학과)
Lim, Il-Hyung (명지대 공대 전기공학과)
Lee, Seung-Jae (명지대 공대 전기공학과)
Choi, Myeon-Song (명지대 공대 전기공학과)
Lim, Seong-Il (경남대 공대 전기공학과)
Kim, Sang-Tae (한전 KDN)
Jin, Bo-Gun (한전 KDN)
Publication Information
The Transactions of The Korean Institute of Electrical Engineers / v.59, no.3, 2010 , pp. 506-514 More about this Journal
Abstract
Defense systems are needed to prevent catastrophic failures of a power grid due to cascaded events. Cascaded events can be occurred by power flow overload. Especially, it is the most dangerous problem that overload line is outage, because it can make the power system face danger of cascaded. In this paper, vulnerability evaluation for monitoring wide are outage is proposed using by configuration information of transmission systems. This method of vulnerability evaluation is considered direct effect and indirect effect of power flow, especially overload. What is more, it can be used when the configuration of power system changes, as simple fault occurs or maintenance of facility. In the case studies, the estimation and simulation network have been testified and analysed in PSSE and C programming.
Keywords
Black-Out; Cascading; Vulnerability; LODF;
Citations & Related Records

Times Cited By SCOPUS : 0
연도 인용수 순위
  • Reference
1 Phadke, A.G and Thorp, J.S. "Expose hidden failures to prevent cascading outages in power systems", Computer Applications in Power. IEEE, pp 20-23, July 1996
2 C. W. Taylor, "Improving Grid Behavior. IEEE Spectrum. June 1999. pp. 40-45.
3 Seong-Il Lim, Chen-Ching Liu, Seung-Jae Lee, Myeon-Song Choi and Seong-Jeong Rim. "Blocking of Zone 3 Relays to Prevent Cascaded Events", Power Systes. IEEE Transactions on Volume 23, pp. 747-754, May 2008.   DOI
4 David C. Elizondo, J. de la Ree, Arun G. Phadke and Stan Horowitz, "Hidden Failures in Protection System and their Impact on Wide-area Disturbances", IEEE, 2001. pp 710-714.
5 J. Chen, J. S. Thorp and M. Parashar. "Analysis of Electric Power System Disturbance Data", Proceedings of the 34th Hawaii International Conference on System Science, 2001.
6 Carson W. Taylor, Bonneville Administration, "Improving Grid Behavior-The inglorious summer-of-1996 blackouts taught the west to improve emergency control and protection and to sharpen simulation techniques", IEEE SPECTRUM JUNE 1999, pp. 42-45.
7 April 2000.U.S.-Canada Power System Outage Task Force, ""Final Report on the August 14, 2003 blackout in the United States and Canada". http://www.ferc.gov/, April, 2004.
8 Seong-Il Lim, Han-Chuan Yuan, Seong-Jeong Rim, Seung-Jae Lee and Myeon-Song Choi "Adaptive Blinder for Distance Relay Based on Sensitivity Factors", IEEE 2006, pp. 22-26.
9 P. Fairley. "The Inruly Power Grid", IEEE Spectrum. pp. 22-27, August 2004.
10 Gregory S. Vassell, Fellow, IEEE, "Northeast Blackout of 1965", IEEE Power Engineering Review, pp. 4-8, January 1991.
11 A.G. Phadke and J.S. Thorp, "Expose Hidden Failure to Prevent Cascading Outages", IEEE Computer Application in Power, pp. 20-23, July 1996.
12 "NIGHT OF TERROR", TIME, pp. 24-26, July 25, 1977.
13 B.A. Carreras, V.E. Lynch, I. Dobson, D.E. Newman, "Critical points and transitions in an electric power transmission model for cascading failure blackout", Chaos, vol. 12, no. 4, December 2002, pp. 985-994.   DOI   ScienceOn