Abstract
The Current transformer is classified measuring CT and protective CT for their purpose. The measuring CT is required to retain a specified accuracy over the normal range of load currents, but the protective CT must be capable of providing an adequate output over wide range of fault condition. Therefore, the protective CT must determine the transient performance during fault condition. This paper measured peak instantaneous error of the TPY class CT to determine the transient performance directly and indirectly and studied the test results.
Keywords
Protective current transformer; Transient performance; Instantaneous error current;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
Times Cited By SCOPUS : 0
연도 인용수 순위
1 "Burdens & Current Transformer Requirements of MiCOM Relays Application Notes", AREVA
2 "CT Analyzer User Manual", OMICRON
3 김동수, 김봉성, 김철환, "단락시험설비의 측정시스템 교정에 관한 연구", 대한전기학회 하계학술대회, 2007
4 IEC 60044-1 Ed.1.2 2003-02 Instrument transformers- Part 1: Current transformers
5 IEC 60044-6 Ed.1.0 1992-03 Instrument transformers- Part 6: Requirements for protective current transformers for transient performance
6 ALEX Y. WU, "The Analysis of Current Transformer Transient Response and Its Effect on Current Relay Performance", IEEE Trans. ON INDUSTRY APPLICATIONS, VOL. IA-21, NO. 4, pp.793-802, 1985   DOI
7 김동수, 김철환, 이기택, 박남옥, "GUI를 이용한 교육용 디지털 거리계전기 시뮬레이터 개발에 관한 연구", Trans. KIEE, Vol. 54A, No.8, pp.390, 2005   과학기술학회마을