Browse > Article

Simulink-based Modelling and Simulation for a Single-phase UPFC  

Kang, Moon-Ho (선문대 공대 정보통신공학부)
Publication Information
The Transactions of The Korean Institute of Electrical Engineers / v.58, no.3, 2009 , pp. 523-530 More about this Journal
Abstract
This paper presents a study on a small scale single-phase UPFC preliminary researches on power quality compensating schemes of electrical railway. As the UPFC is very complicated power-electronic system consisting of grid-connected transformers, four single phase inverters interconnected with dc-link capacitors and various electrical apparatuses, multiple controllers and control algorithms are needed, and entire UPFC has been modelled in the form of block diagrams and simulated by using Simulink. The main purpose of the compensating system is to manage reactive and active powers with the four single phase inverters, so, the control effort has been focused on the power flow control and has been realized through the hysteresis current control of the single phase inverters. And transport-delayed PLL with additional delay-time compensating term has been used to synchronize a grid voltage and the simulation results have shown that the compensating term could improve PLL performance under some frequency variation of the voltage.
Keywords
UPFC; Single phase inverter; Simulink; Power flow control; PLL;
Citations & Related Records

Times Cited By SCOPUS : 2
연도 인용수 순위
1 L. Gyugyi, et aI., 'The Unified Power Flow Controller:A New Approach to Power Transmission Control', IEEE Trans. on Power Delivery, Vol.10, No.2, pp.1085-1097, Apr. 1995   DOI   ScienceOn
2 D. Sutanto, et aI., 'Hysteresis Control over UPFC', APSCOM 2000, HK, Oct. 2000, 376-379   DOI
3 M. Ciobotaru, et aI., 'Improved PLL Structures for Single-phase Grid Inverters', Proceedings of PELINCEC 2005,. 16-19 Oct. 2005
4 Clarissa Gatlan and Leonard Gatlan, 'AC to DC PWM Voltage Source Converter under Hysteresis Current Control', ISIE'97, Portugal, 469-473, 1997
5 K. L. Mok, et aI., 'EMTP simulation of a STATCOM using Hysteresis Control', APSCOM 2000, HK, pp. 522-526, Oct. 2000
6 G. Hsieh, and J,C. Hung, 'Phase-lock ed loop techniques - a survey', IEEE Trans. on Industrial Electronics, vol. 43, no. 6, pp. 609-615, 1996   DOI   ScienceOn
7 C. D. Schauder, et aI., 'Operation of the Unified Power Flow Controller(UPFC) Under Practical Constraints', IEEE Trans. on Power Delivery, Vol.13, No.2, pp.630-639, Apr. 1997   DOI   ScienceOn
8 MathWorks, Simulink Simulation and Model-Based Design
9 MathWorks, SimPowerSystems for Use with Simulink-User's Guide Version 4
10 Kalyan K. Sen and Eric J, Stacey, 'UPFC-Unified Power Flow Controller:Theory, Modeling, and Application', IEEE Trans. on Power Delivery, Vol.13, No.4, pp.1453-1460, Oct. 1998   DOI   ScienceOn
11 박현준 외, Smart-Rail 기술개발(전기/궤도토목), 차세대 철도원천 기술개발 보고서, 한국철도기술연구원, 2003
12 송의호 외, 'EMTDC를 이용한 UPEC Simulation', 전력전자학회 논문지, 6권, 3호, pp.291-295, 2001   과학기술학회마을
13 S.M. Silva, et. aI., 'Performance Evaluation of PLL Algorithms for Single-phase Grid-connected Systems', Proc.of IAS'04, vol. 4, pp. 2259-2263. 2004   DOI
14 M.H. Kang and Y.C. Park, 'A real-time control platform for rapid prototyping of induction motor vector control', Electrical Engineering, vol.88, no.6, pp. 473-483, Aug. 2006   DOI   ScienceOn