The Mechanical and Electrical behavior Changes of Overhead Conductor due to Forest Fire and Agents  

Jang, Young-Ho (한국전기연구원)
Kim, Byung-Geol (한국전기연구원)
Kim, Shang-Shu (한국전기연구원)
Han, Se-Won (한국전기연구원)
Kim, Jin-Han (경남지방중소기업청)
Publication Information
The Transactions of The Korean Institute of Electrical Engineers / v.58, no.2, 2009 , pp. 242-247 More about this Journal
Abstract
Forest Fire can cause a serious damage to overhead conductors. Therefore, the detailed investigation for the changes of mechanical and electrical properties of damaged conductors should be carried out to understand the effect of forest fires on conductors. This is very much important to maintain transmission line safely. Oxidation of overhead conductor was increased with temperature and time(maximum time : 30min). Conductivity of Al conductor was decreased by Agents. The detailed will be given in the text.
Keywords
ACSR $410mm^2$; Forest fire; Agents; Electrical property; Mechanical property;
Citations & Related Records
Times Cited By KSCI : 6  (Citation Analysis)
Times Cited By SCOPUS : 1
연도 인용수 순위
1 P. H. Schwabe and D. Pike, 'The Measurement of Corrosion in Overhead Power line'. ANTICorrosion, 1988
2 김병걸외 2명, '고강도 저손실 가공송전선 개발-기계적특성', 전기전자재료학회논문지, 18권 12호, p.1152, 2005   과학기술학회마을   DOI   ScienceOn
3 김상수외 2명, '고강도 저손실 가공송전선 개발-전기적특성', 전기전자재료학회논문지, 18권 12호, p.1159, 2005   과학기술학회마을   DOI   ScienceOn
4 깁병걸외 3명, '산불에 의한 가공송전선의 영화거동', 전기전자재료학회논문지, 2007 20:1105-1111   과학기술학회마을   DOI   ScienceOn
5 김상수외 4명, '가공송전선의 열적거동과 전류 및 외기 온도의 영향', 전기전자재료학회논문지, 2006, 19:486-491   과학기술학회마을   DOI   ScienceOn
6 김병걸외 5명, '환경적 요인에 의한 노후 가공송전선의 특성변화', 전기전자재료학회논문지, 2006 19:287-291   과학기술학회마을   DOI   ScienceOn
7 김병걸외 2명, 'STACIR/AW 송정선의 장시간 운전에 따른 기계적 물성 변화', 한국전기전자재료학회 2004 하계학술대회논문집, p.1258, 2004   과학기술학회마을
8 김영달, '화염에 의한 ACSR 송전선의 표면 특성에 관한 연구', 조명.전기설비학회지, 17권, 6호, p. 173, 2003   과학기술학회마을   DOI   ScienceOn