Abstract
In this paper, current limiter using a magnetic switching which is based on magnetic flux change in the case of fault is proposed. This current limiter consists of iron-core and three parts of coils. One is the primary coil connected to the power system. Another is the secondary coil wound to the opposite direction of the primary coil's winding. The other is the secondary of the secondary coil which is a movable copper plate winding and located below the secondary coil. In the normal state, the magnetic flux produced in the primary and secondary coils flows to the opposite directions each other and becomes to be canceled out. Therefore the voltages induced between the coils are zero. In the case of a fault, at the moment of a fault occurrence recognition, the switch connected to a secondary coil is opened and the secondary of the secondary coil is pulled out to the outside of the iron-core. Then, magnetic flux becomes to flow through the iron-core. Accordingly, the voltage is induced between the both ends of the primary coil and makes the current reduced. Therefore it is possible to cut off the circuit breaker easily with the proposed current limiter. This paper analyzes the current limiting effects and the detailed results are given.
Keywords
Current Limiter; Fault Current; Magnetic Switching; Circuit Breaker; Magnetic Flux; Phasic Similitude; Magnetic Circuit;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
Times Cited By SCOPUS : 0
연도 인용수 순위
1 S. H. Lim, 'Fault Current Characteristics due to Winding Direction between Coil 1 and Coil 2 in a flux-lock type SFCL', Phys. C, vol.416, pp.34-42, November 2004   DOI   ScienceOn
2 임성훈, '코일의 직·병렬 결합을 이용한 초전도 사고전류제한기의 동작전류 증가', Journal of the Korean Institute of Illuminating and Electrical Installation Engineers, Vol.21, No.10, pp.46-51, December 2007   과학기술학회마을   DOI   ScienceOn
3 지근양, 'Magnetic Switching을 이용한 직류회로 순간 전류제한기', 대한전기학회 전력기술부문회 추계학술대회 논문집, pp.28-30, 2008   과학기술학회마을
4 David K. Cheng, 'Fundamentals of Engineering Electromagnetics', 김남.윤영로.전석희.전호인 공역, pp.222-232, 1995
5 C. H. Flurscheim, 'Power circuit breaker theory and design', Peter Peregrinus, pp.189-234, 1985
6 S. H. Lim, 'Fault Current Characteristics of New Resistive Type Superconducting Fault Current Limiter using Flux Linkage', Phys. Stat. sol. (c), vol. 2, no. 5, pp.1755-1760, March 2005   DOI   ScienceOn
7 임성훈, '차폐유도형 고온초전도 전류제한기의 설계 및 특성시뮬레이션', 전북대학교 공학연구 제29호, pp.165-171, 1998