Abstract
Most faults are single-phase-to-ground fault in ungrounded system. The fault currents of single-phase-to-ground are much smaller than detection thresholds of measurement devices, so detecting single-phase-to-ground faults is difficult and important in ungrounded system. This paper proposed to a FI(Fault Indicator) generation algorithm in ungrounded system. The algorithm just using line-to-line voltage and zero-sequence current detects fault line, fault phase, fault section and FI(Fault Indicator) at terminal device, This paper also proposed to application plan for this algorithm. In the case study, the proposed algorithm has been testified in demo system by Matlab/Simulink simulations.
Keywords
Distribution System; Distribution Automation; Ungrounded System; FI; Fault Indicator; Zero-Sequence Current;
Citations & Related Records

Times Cited By SCOPUS : 0
연도 인용수 순위
  • Reference
1 Hong-chun Shu, Bai Xiao, 'A novel fault line selection algorithm of single-phase ground faults in ungrounded neutral system using wavelets transform', PowerCon 2002, Vol.4, pp. 2532-2536, Oct. 2002
2 Bingyin Xu, Yongduan Xue, Jing Li, Yu Chen, 'Single phase fault detection technique based on transient current and its application in non-solid grounded network', IEE 2001 Conference in Developments in Power System Protection, No.429, 2001
3 하복남 외6, The Development of the New Distribution Automation System, KEPRI '98 전력연-단663, 1998
4 박영문, 김재철, 전력계통기술계산 응용, 도서출판 의제, 1998
5 Chengyong Zhao, Yanfen Guo, Gengyin Li, 'The similitude power detection on single phase-to-ground fault in the non-solidly grounded system', IEEE/PES Transmission and Distribution Conference & Exhibition: Asia and Pacific Dalian, China, pp. 1-5, 2005
6 In Sun Choi, Myeon Song Choi, Seong Il Lim, Seung Jae Lee, 'A new algorithm of the line to ground fault section isolation & restoration in ungrounded distribution power system', Trans. KIEE. Vol. 53A, No. 10, Oct. 2004
7 Qianli Su, XinzhouDong, Shenxing Shi, Bin Su, Jiali He, 'A new principle of fault line selection for distribution', Seventh International Conference on (IEE) Developments in Power System Protection, pp. 89-93, June 2004
8 Baldwin, T.; Renovich, F., 'Analysis of fault locating signals for high-impedance grounded systems', IEEE Transactions on Industry Applications, Vol. 38 No. 3, pp. 810-817, May/Jun 2002   DOI   ScienceOn
9 Z. Q. Bo, G. Weller, M. A. Redfern, 'Accurate fault location technique for distribution system using fault-generated high-frequency transient voltage signals', IEE Proceedings on Generation, Transmission and Distribution, Vol. 146, issue 1, pp. 73-79, Jan. 1999
10 Baldwin, T.; Renovich, F.; Saunders, L., 'Directional ground fault indicator for high-resistance grounded systems', 2002 IEEE Industrial and Commercial Power Systems Technical Conference, pp. 103-109, 2002
11 Baldwin, T.; Renovich, F., Jr.; Saunders, L.F.; L.F.; Lubkeman, D., 'Fault locating in ungrounded and high-resistance grounded systems', IEEE Transactions on Industry Applications, Vol. 37 No. 4, pp. 1152-1159, July-Aug. 2001   DOI   ScienceOn
12 Leel Ho Seol, Bok Nam Ha, Mi Ae Jeong, Moon Ho Kang, Sang Ho Lee, 'A study of line-to-ground fault solution in ungrounded network base on the distribution automatic system', KIEE summer conference, July 14-16, 2004