Browse > Article

Development of a Calculable Potential Transformer with Wide Ratio Error  

Kwon, Sung-Won (한국표준과학연구원 기반표준부 전자기센터)
Jung, Jae-Kap (한국표준과학연구원 기반표준부 전자기센터)
Lee, Sang-Hwa (한국표준과학연구원 기반표준부 전자기센터)
Kim, Myung-Soo (한국표준과학연구원 표준보급부)
Publication Information
The Transactions of The Korean Institute of Electrical Engineers / v.57, no.6, 2008 , pp. 1017-1021 More about this Journal
Abstract
A calculable potential transformer(PT) with nominal ratio error in wide range of -10% to +10% has been developed on basis of theoretical calculation of ratio error by the number of windings. The developed PT can be used to evaluate the linearity and accuracy of the PT comparator by comparing both the theoretical and experimental values of the PT which have exactly same ratio errors in nominal and calculated values. The PT has been applied for calibration and correction of the PT comparator up to wide ratio error range of -10% to +10%. This portable PT is very convenient to carry to the power industry for the on-site calibration of the PT comparator.
Keywords
Calculable potential transformer(PT); Wide ratio error PT; PT comparator; On site calibration; linearity;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
Times Cited By SCOPUS : 0
연도 인용수 순위
1 정재갑, 권성원, 김규태, 김명수, "외부부담이 전압변성기의 비오차와 위상각오차에 미치는 영향에 대한 연구", 대한전기학회지, vol. 53C, No. 3, pp 137-142, 2004
2 권성원, 정재갑 등, "초정밀 광범위 비오차 전압변성기의 개발 및 그 응용", 대한전기학회지, vol. 55C, No. 6, pp 317-322, 2006   과학기술학회마을
3 IEEE Standard Requirements for Instrument Transformers, American National Standards Institute, ANSI/IEEE C57, No. 13, pp. 45-46, 1978
4 J. L. Settles, W. R. Farber, and E. E. Connor, "The analytical and graphical determination of complete potential transformer characteristics" IEEE Trans. Power Apparatus and Systems, vol. 79, No. 51, pp. 1213-1218, 1961
5 Certificate of the PT comparator, Zera model WM 303U, PTB, 2005
6 계기용변성기, KSC 1706
7 정재갑, 권성원 등, "넓은 범위의 비오차를 갖는 전압변성기를 이용한 계기용 변성기 비교측정 장치의 비오차 직선성 평가기술", 대한전기학회지, vol. 53C, No. 3, pp 137-142, 2004