Browse > Article

$SF_6$ Emission Characteristics at High Voltage Equipments in use-phase Stage  

Park, Jung-Ju (서울시립대학교 환경공학부)
Cha, Yeun-Haeng (한국산업기술시험원 환경기술본부)
Publication Information
The Transactions of The Korean Institute of Electrical Engineers / v.57, no.12, 2008 , pp. 2199-2201 More about this Journal
Abstract
Sulfur hexafluoride($SF_6$) is a gaseous dielectric used in high voltage electrical equipment such as an insultor or arc quenching medium in the transmission and distribution of electricity. however, $SF_6$ is one of the greenhouse gases(GHG) with a global warming potential that is 23,900 times greater than that of carbon dioxide($CO_2$). for this reason, $SF_6$ emissions in electric equipment shall be controlled to reduce GHG and improve cost-effective use of $SF_6$ for economical benefits. Until recently there has not been any investigation on $SF_6$ emission characteristics and inventory in Korea. To understand emission characteristics during the use-phase, the scope of this study was limited to the following closed pressure system equipment from 10 substations in Korea. This study highlights (1) the investigation of sampling/analysis methodology for $SF_6$ emissions in high voltage equipment, (2) the estimation of $SF_6$ emissions in the use-phase, and (3) the comparison between the emission ratio and the mass-balance applied to inventory study. According to this study, the majority of emissions were related to electric equipment nameplates and the rest of the emissions were related to the handling of $SF_6$ during operations. from this result, emission ratios estimated from this study were similar; GIS was 14% and GCB was 13%, as maintenance process conditions were the same as manual process conditions for both equipment.
Keywords
Sulfur hexafluoride($SF_6$); $SF_6$ life cycle; High voltage equipment;
Citations & Related Records

Times Cited By SCOPUS : 0
연도 인용수 순위
  • Reference
1 Sina, W., and Jochen, H., Reductions of $SF_6$ Emissions from High and Medium Voltage Electrial Equipment in Europe, Ecofys, June, 2005
2 Blackman, J., and Mueller, B., Managing your $SF_6$ Gas Inventory-$SF_6$ Emission Reduction Partnership Webcast, U.S. EPA, May, 2007
3 CAPIEL, Switchgear and $SF_6$ Gas, HV-ESDD1-R1-1.02, January, 2002
4 電気事業連合會, $SF_6$ ガス液化回収装置によるガス回収時間, March, 20
5 電気事業連合會, (社) 日本電機工業會, (社) 日本$_\circ$化學 工業協會, $SF_6$ ガスの回収 . 再利用の促進万策につい て, カ . メーカ共同検討會報告書, August, 2000