Abstract
According to the increase of power demand and expansion of downtown, it is necessary to install transformers additionally in operating substations and construct substations in residential area. But the public complaint is increased due to the transformer noise of the substation. KEPCO has used a vibration preventing pad, various soundproof walls and an encloser to transformers in outdoor substations, and a soundproof door, shutter and wind-path soundproof equipment in indoor substations to block the sound propagation of the transformers. But these noise reduction methods are not satisfied. It should be considered to reduce transformer noise itself. In this paper, we investigated core noise reduction techniques to develope a low noise transformer. The techniques to reduce core noise of the transformer are application of high permeability grain oriented silicon sheets, decrease of magnetic flux density of core, application of 6step-lap core stacking method, improvement of core binding method(binding addition, band fixing) and application of rubber damper in oder to reduce transmission of core vibration, etc.
Keywords
Transformer; Core; Noise; Vibration; Step lap;
Citations & Related Records

Times Cited By SCOPUS : 0
연도 인용수 순위
  • Reference
1 Toshiaki Yanada, shunataro Munowa, Osamu Ichinokura and shink kikuchi, 'Design and Analysis of Noise-Reduction Transformer Based on Equivalent Circuit,' IEEE Transaction on Magnetics, pp. 1351-1353, 1998
2 'AK Steel Oriented And TRAN-COR H.(ELECTRICAL STEELS),' AK Steel Corporation Electrical Steels, USA, 1999
3 권동진, '저소음 변압기 개발을 위한 기초 조사 연구 보고서,' 전력연구원, pp. 1-92, 2004
4 김연환, '신마산 전력소 345kV 변압기 소음평가,' 전력 연구원, pp. 1-12, 2000
5 Hiroyuki Matsuoka, Takao Shimada, 'Recent Noise Reduction Techniques for Power Transformers,' 環境調和技術, pp. 41-44, 1996
6 '변압기의 소음레벨 기준치,' 한국전력 표준규격(ES147), 2006
7 Rober F.Wolff, 'Drown out transformer noise(USA),' Power Delivery, pp. 83-85, 1983
8 권동진, '저소음 변압기 제작 및 적용실태 조사 관련 일본출장보고서,' 전력연구원, pp. 1-31, 2004
9 김연환, 이현, 김수형, '154kV 남광주 변전소 소음영향 평가,' 전력연구원, pp. 1-9, 1999
10 이준신, '의정부변전소 소음저감방안 적용연구,' 전력연구원, pp. 1-60, 2003
11 '생활소음 . 진동의 규제,' 소음 . 진동규제법 제39조, 1993
12 B.Weiser, H.Pfutzer and J.Anger, 'Relevance of Magnetostriction and Force for the Generation of Audible Noise of Transformer Cores,' IEEE Transaction on Magnetics, Vol 36, No.5, pp. 3759-3777, 2000   DOI   ScienceOn