Abstract
The one step type pole and two step type pole are used in KEPCO's distribution system. The neutral current increases in three-phase four-wire distribution system due to unbalanced load. Usually, power line and communication line are installed at contiguity by effect of topography in Korea. To this end, the damages such as electrostatic induction, electromagnetic induction and harmonic induction generated by induced voltage and current are occured in power line and communication line. This paper calculates the neutral current in KEPCO's distribution system using EMTP by composing various simulated conditions. Also, these results are verified by vector analysis.
Keywords
One Step Type Pole; Two Step type Pole; Neutral Current; Vector Analysis; EMTP;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
Times Cited By SCOPUS : 0
연도 인용수 순위
1 서훈철, 권오상, 김철환, 정창수, 유연표 '가공 배전선로 장주의 중성선 전류 계산', Trans, KIEE, Vol 55A, No 7, pp.290-296, Jul 2006   과학기술학회마을
2 '실배전 계통 모델을 이용한 2단중주 중성선 불평형 전류와 전력유도 상관관계 분석', 한국 전력 공사, 2005. 11
3 Thomas M. Gruzs, 'A survey of neutral currents in three-phase computer power systems,' IEEE Trans. on Industry Application, Vol. 26, No.4, pp.719-725, 1990   DOI   ScienceOn
4 J.C. Balda, A.R. Oliva, D.W. McNabb, R.D. Richardson, 'Measurements of Neutral Currets and Voltage On a Distribution Feeder', IEEE Trans. on Power Delivery, Vol. 12. No. 4, October 1997