Browse > Article

Neutral Current Calculation of the One Step Type Pole using KEPCO's Distribution System  

Seo, H.C. (기초전력연구원 전력시스템연구실)
Park, K.W. (성균관대 대학원 전자전기공학과)
Kim, C.H. (성균관대 정보통신공학부)
Jung, C.S. (한국전력공사 전자통신처)
Yoo, Y.P. (한국전력공사 포항지점 배전운영)
Lim, Y.H. (한국전력공사 전력통신그룹)
Seol, I.H. (한국전력공사 전북지사)
Publication Information
The Transactions of The Korean Institute of Electrical Engineers / v.56, no.1, 2007 , pp. 35-40 More about this Journal
Abstract
The one step type and two step type pole are used in distribution line. If the three phases are not balanced, the communication line can be damaged by induced voltage. This paper calculates the neutral current using KEPCO's distribution system model which is only composed by one step type pole. The used system model is modelled by using ATPDraw and the neutral current is calculated by using EMTP/MODELS. Many cases for abstracting the neutral current characteristics in KEPCO's distribution system are simulated and analyzed.
Keywords
Neutral Current; One step type pole; Distribution system; ATPDraw; Unbalanced rate;
Citations & Related Records

Times Cited By SCOPUS : 1
연도 인용수 순위
1 David E. Johnson, John L. Hilburn, Johnny R. Johnson, Peter D. Scott, ' ELECTRIC CIRCUIT ANALYSIS', PRENTICE HALL