Browse > Article
http://dx.doi.org/10.5370/KIEEP.2017.66.1.021

A Study on the Application of Under Voltage Load Shedding Scheme in Line Contingency considering Motor Load  

Lee, Yun-Hwan (Coon Tec)
Publication Information
The Transactions of the Korean Institute of Electrical Engineers P / v.66, no.1, 2017 , pp. 21-26 More about this Journal
Abstract
Failure of high-voltage transmission line, which is responsible for large-scale power transmission, can be reason for system voltage instability. There are many methods to prevent voltage instability like adjustment of equipment, the generator voltage setting, and load shedding. Among them, the load shedding, have a problem of economic loss and cascading effect to power system. Therefore, the execution of load shedding, amount and timing is very important. Conventionally, the load shedding setting is decided by the preformed simulation. Now, it is possible to monitor the power system in real time by the appearance of PMU(Phasor Measurement Unit). By this reason, some of research is performed about decentralized load shedding. The characteristics of the load can impact to amount and timing of decentralized load shedding. Especially, it is necessary to consider the influence of the induction motor loads. This paper review recent topic about under voltage load shedding and compare with decentralized load shedding scheme with conventional load shedding scheme. And simulations show the effectiveness of proposed method in resolving the delayed voltage recovery in the Korean Power System.
Keywords
Voltage stability; Phasor measurement unit application; Under voltage load shedding scheme;
Citations & Related Records
Times Cited By KSCI : 3  (Citation Analysis)
연도 인용수 순위
1 B. Hoseinzadeh, F. Faria Silva, and C. Leth Bak, "Adaptive tuning of frequency thresholds using voltage drop data in decentralized load shedding", Power Systems, IEEE Transactions on, vol. 30, no. 4, pp. 2055-2062, July 2015.
2 B. Hoseinzadeh, F. Faria Silva, and C. Leth Bak, "Decentralized coordination of load shedding and plant protection considering high share of RESs", Power Systems, IEEE Transactions on, 2015.
3 Sachin K. Jain, Preeti Jain, Sri Niwas Singh, "A Fast Harmonic Phasor Measurement Method for Smart Grid Applications", IEEE Transactions on Smart Grid, vol. 8, no. 1, Jan, 2017.
4 Emily R. Fernandes, Scott G. Ghioce, "Application of a Phasor-Only State Estimator to a Large Power System Using Real PMU Data", IEEE Transactions on Power Systems, vol. 32, no. 1, Jan, 2017.
5 Michael W. Fisher, Ian A. Hiskens, "Phase Boundary Computation for Fault Induced Delayed Voltage Recovery", 2015 IEEE 54th Annual CDC, 2015.
6 Zhang Yue1,a, Li Xiaoming, "Dynamic Voltage/Var Sensitivity Approach for Improving Fault-induced Voltage Delayed Recovery Problems", International Power, Electronics and Materials Engineering Conference, 2015.
7 Krishnanjan Gubba Ravikumar, Scott Manson, "Analysis of Fault-Induced Delayed Voltage Recovery Using EMTP Simulations", IEEE PES Transmission and Distribution Conference and Exposition, 2016.
8 KPX, "Power System Operation Guide", 2012.
9 Jeonghoon Shin, Suchul Nam, Jaegul Lee, Youngdo Choy, Taekyun Kim, Hwachang Song, "Application of Multi-step Undervoltage Load Shedding Schemes to the KEPCO System" Journal of Electrical Engineering & Technology, vol. 4 no. 4, p. 476-484, 2009.   DOI
10 Jeonghoon Shin, Suchul Nam, Seungmook Baek, Jaegul Lee, Seungpil Moon, Taekyun Kim, "Study on the Development of Load Shedding Scheme for Improving Voltage Stability of Seoul Metropolitan Area using Synchro-phasor Data", Trans. KIEE. vol. 59, no. 9, SEP, 2010.
11 Yunhwan Lee, "Using the Under Voltage Load Shedding for Stability Enhancement of Power Systems Considering Induction Motor Load", The Transactions of the Korean Institute of Electrical Engineers vol. 65P, no. 1, pp. 1-6, 2016.
12 Prabha Kundur, "Power System Stability and Control", 1994.