Analysis and Performance Test of Hybrid Transformer used in the Grid-Connected Photovoltaic Generation System  

Kim, Ji-Ho ((주)에너테크 기술연구소)
Park, Hoon-Yang ((주)에너테크)
Shon, Jin-Geun (가천대학교 전기공학과)
Publication Information
The Transactions of the Korean Institute of Electrical Engineers P / v.63, no.4, 2014 , pp. 333-338 More about this Journal
Abstract
This paper concerns the development of the transformer that can reduce harmonics supplied to the system if the output of photovoltaic inverter in the photovoltaic system is grid-connected, and suggests that problems of harmonics and power factor degradation in the grid-connected photovoltaic system can be improved. In this study, the burden of increasing the investment in new facilities and securing their installation space due to harmonics has been substantially eased through the development of a hybrid transformer possessing unbalanced function and harmonics reduction function using zig-zag coils, and most of all, it is expected that the development of such high efficiency hybrid transformer possessing functions of transformation and reducing harmonics can improve the power quality as well as prevent damages caused by harmonics, leading to suppress unnecessary loss of electric power and thereby contribute to energy savings.
Keywords
Harmonics; Hybrid transformer; Photovoltaic system; Smart grid; Zig-zag winding;
Citations & Related Records
Times Cited By KSCI : 4  (Citation Analysis)
연도 인용수 순위
1 J.I Jang, D.C. Lee, H.G. Kim, "Current Control of Three-Phase PWM Converters under Unbalanced and Distorted Source Voltage", Journal of power electronics, Vol 12, No. 1, 2007.02.   과학기술학회마을
2 P.P. Khera, "Application of zig-zag transformers for reducing harmonics in the neutral conductor of low voltage distribution system" Industry Applications Society Annual Meeting, Conference Record of the IEEE, 7-12pp. 1092 vol.2, Oct.1990.
3 K.C Kim, "A Study on the Harmonics Reduction using Phase Shifting Transformer in a Electric Power Distribution System", Journal of the korean institute of llluminating and Electrical installation Engineers Vol, 16.No 2,pp. 38-44 March 2002   과학기술학회마을   DOI   ScienceOn
4 Y.B Song, Y.H Cho, D.J Choi, "Development of the Harmonics Reduction and Energy Saving Equipment in Variable Loads", Journal of the Korean Institute of IIIuminating and Electrical Installation Engineers Vol. 20, No.6, pp. 87-95 July 2006   과학기술학회마을   DOI   ScienceOn
5 Y.H Min, D.C Shin, "A study on the Development of the Shell-type Pole Transformer Using the Zig-Zag Winding", Journal of the korean institute of llluminating and Electrical installation Engineers Vol, 21.No 8, pp. 121-128 March 2007   과학기술학회마을   DOI   ScienceOn
6 A.A. Mohmoud, R.D. Shaltz, "A method for analyzing harmonic distribution in AC power systems". IEEE Trans., PAS-101, pp151-161, Aug. 1982.