Browse > Article

Characteristics Analysis of Capacitor and Reactor for Harmonic Filter  

Kim, Jong-Gyeum (강릉대학교 전기정보통신공학부)
Park, Young-Jeen (강릉대학교 전기정보통신공학부)
Lee, Eun-Woong (충남대학교 전기공학과)
Publication Information
The Transactions of the Korean Institute of Electrical Engineers P / v.58, no.1, 2009 , pp. 1-8 More about this Journal
Abstract
Recently, application of non-linear load is gradually increased. Non-linear load produces harmonic components of current during the energy conversion transition. Passive filter is used for reducing of harmonics in the user power systems. This filter, which is composed of capacitor and reactor, frequently get out of order by electrical stress. There are voltage and current increase when capacitor and reactor are applied in the user's filter systems. If increased voltage and current is above stipulated values, they have severely an influences on the life of capacitor and reactor. This paper describes that the voltage and current of capacitor used for filter is within the limits of allowable values, but reactor is beyond the limits and reveals spike voltage. Therefore this phenomenon brings about premature fault of reactor and capacitor.
Keywords
Harmonics; Filter; Non-Linear Load; Capacitor; Reactor;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 KSC 4802, "고압 및 특별고압 진상 콘덴서". 1997
2 KSC 4801, "저압 진상콘덴서", 2003
3 JIS C-4902, "고압 및 특별고압 진상 콘덴서 및 부속기기", 1998
4 JIS C-4901, "저압 진상 콘덴서", 2000
5 IEC 60831, "Shunt power capacitors of the self-healing type for AC systems having a rated voltage above 1000V"
6 Thomas M, Blooming, "Capacitor Application Issues", IEEE Trans on LAS, Jul-Aug, pp. 1013-1026, 2008
7 김종겸, 이은웅, 이동주, "불평형 전압으로 운전하는 비선형 부하의 고조파 특성 분석" 대한전기학회 논문지(B) 제 52권 10호, No. 10, pp.491-500, 2003.10   과학기술학회마을   ScienceOn
8 IEC 60871, "Shunt power capacitors of the self-healing type for AC systems having a rated voltage above 100V", 2005.07
9 C. Boonseng et al., "Failure Analysis of Dielectric of Low Voltage Power Capacitors Due to Related Harmonic Resonance Effects", IEEE Power Engineering Society Winter Meeting, Volume 3, 28 Jan-Feb. pp.1003-1008, 2001
10 H.W. Dommel, "Electromanetic Transients Program. Referene Manual(EMTP Thery Book)", BPA 1986
11 IEC 60076-6, "Power transformers-reactor", 2007.12
12 IEEE Std 18-2002, "IEEE Std for Shunt Power Capacitor"
13 KSC 4806, "고압 및 특별 고압 진상 커패시터용 직렬리액터", 2004
14 V. E. Wagner et al., "Effects of Harmonics on Equipment", IEEE Trans on PD, Vol. 8, No.2, pp.672-680, 1993. April   DOI   ScienceOn