Establishment of National Standard System for 20.000 A Current Transformer  

Jung, Jae-Kap (한국표준과학연구원)
Lee, Sang-Hwa (한국표준과학연구원)
Kang, Jean-Hong (한국표준과학연구원)
Kim, Myung-Soo (한국표준과학연구원)
Kim, Yoon-Hyoung (충남대학교 전기공학과)
Han, Sang-Gil (충남대학교 전기공학과)
Han, Sang-Ok (충남대학교 전기공학과)
Publication Information
The Transactions of the Korean Institute of Electrical Engineers P / v.57, no.1, 2008 , pp. 6-13 More about this Journal
Abstract
National standard system for calibrating current transformer(CT) up to primary current of 20,000A have been established. The system consists of 20,000 A AC high current source, CT comparator, standard CT, CT under test and CT burden. An AC high current is applied tn the primary windings of both the standard CT and the CT under test, and then the CT comparator measures the ratio error and the phase displacement by comparing the secondary currents of the two transformers. As a validity check for 20,000 A CT calibration system, the comparison with the two national standard institutes(NMIs) has been performed using same CTs. The comparison results of the CTs are consistent with those measured at two NMIs within 0.004 % for ratio error and 0.1 min for phase displacement in the primary current ranges of Ip = 10 - 20,000 A with a secondary current of Is = 5 A.
Keywords
National standard system; Current transformer; CT comparator; Ratio error; Phase displacement; CT burden;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 Gun-Woo Moon and Suk-Ho Yoon, "Predictive current control of distribution static condenser (D-STATCON) for reactive power compensation in flexible AC transmission system (FACTS)" Power Electronics Specialists Conference, PESC 98 Record. 29th Annual IEEE, vol. 1, 816-822(1998)
2 Calibration result of P-5000 current transformer(S/N : 0490961) in NMIA (Report No: 48289, 2005)
3 Calibration report of current transformer (Type : NCD 20000d, S/N : 2/06/0006) in PTB (Reference No: 2.31-06000359, Calibration mark : 2183 PTB 06)
4 K. R. Padiyar and A. M. Kulkarni, "Analysis and design of voltage control of static condenser" Power Electronics, Drives and Energy Systems for Industrial Growth, Proceedings of the International Conference on Publication vol. 1, 393-398(1996)
5 정재갑, 이상화, 권성원, 강전홍, 김명수 "전류변성기 비교측정 장치의 현장 평가 기술", 대한전기학회지, 56권(5호). 926-932(2007)   과학기술학회마을
6 한국표준협회, "계기용변성기(표준용 및 일반계기용)", KS C 1706, 1982
7 I. E. Zinn "PTB testing instructions instrument transformers" PTB testing instructions 12, ISSN 0341-7964, 85-86(1977)
8 S. S. Kumar, V. Subbiah, A. Kandaswaray, G. D. Kumar, R. Sujay, S. Manoharan, "A state of the art ST ATCON for instantaneous VAr compensation and harmonic suppression to enhance power quality" Quality and Security of Electric Power Delivery Systems, CIGRE/IEEE PES International Symposium, 86-90(2003)