Browse > Article

Signal Characteristics of Ultra-high Frequency Radiation from Partial Discharge in Insulation Oil  

Ju, Hyoung-Jun (한전 전력연구원)
Goo, Sun-Geun (한전 전력연구원)
Park, Ki-Jun (한전 전력연구원)
Han, Ki-Seun (한전 전력연구원)
Yoon, Jin-Yul (한전 전력연구원)
Publication Information
The Transactions of the Korean Institute of Electrical Engineers P / v.57, no.1, 2008 , pp. 56-59 More about this Journal
Abstract
We have designed 4 types(void in insulation paper, protrusion electrode, floating electrode, surface discharge) of partial discharge(PD) defect to simulate typical faults found in oil filled power transformers. Ultra-high frequency(UHF) radiation due to PD was measured using a UHF measuring system and a conventional PD measuring system, simultaneously. Electromagnetic radiation spectra of these defects show UHF radiation up to about 1.5-2 GHz range. The phase resolved partial discharge(PRPD) patterns of UHF radiation from the PD defects were also measured and the pattern reveals distinct feature for each defect types. The UHF measuring could be used to detect PDs in oil filled transformers and analysis of the PRPD pattern should provide useful information on origin of PD signal.
Keywords
Partial Discharge; Insulation Oil; UHF PD signal; PD detection;
Citations & Related Records
연도 인용수 순위
  • Reference
1 S. Meijer, E. Gulski, J. J. Smith, & H. F. Reijnders, "Sensitivity Check for UHF PD Detection on Power Transformer", 2004 IEEE International Symposium on Electrical Insulation, Indianapolis, 19-22 Sep., 2004
2 C. R. Li, W. Wang, Z. G. Tang & Y. S. Din, "PD Pattern Recognition in Transformer by Using UHF Technology", 2004 IEEE International Symposium on Electrical Insulation, Indianapolis, 19-22 Sep., 2004
3 M. Wang, A. J. Vandermaar, and K. D. Srivastava, "Review of condition assessment of power transformers in service," IEEE Elect. Insul. Mag., vol. 18, no. 6, pp. 12-25, Nov./Dec. 2002
4 윤진열, 박기준, 구선근, "GIS 고장예방을 위한 UHF 부분방전 신호해석기술 연구", 전력산업연구개발사업 최종보고서, 한국전력공사 전력연구원, May, 2005
5 K. Raja, F. Devaux & S. Lelaidier, "Recognition of Discharge Sources Using UHF PD Signatures", IEEE Electrical Insulation Magazine, pp8-14, Vol. 18, No. 8, Sep., 2002
6 M. D. Judd, B. M. Pryor & B. F. Hampton, "Transformer Monitoring Using the UHF Technique". High Voltage Engineering Symposium, 5.362.P5, 22-27 Aug., 1999
7 IEEE,C57.113, "Guide for Partial Discharge Measurement in Liquid-Filled Power Transformers and Shunt Reactors", 1991
8 G. Wanninger, "Apparent charge measurement in GIS by modem diagnostic methods," Eur. Trans. Elect. Power, pt. 4, vol. 7, pp. 251-255, jul./Aug. 1997
9 윤진열, 박기준, 구선근, "GIS 부분방전 검출기술연구", 한국전력공사 전력연구원, TR 98J2002.407. 2002
10 윤진열, 박기준, 구선근, "GIS내 자유 도전성 파티클 결함에 대한 위험도 평가방안", 대한전기학회지 Vol.51C. No.4. Apr.2002
11 M. D. Judd, J. S. Pearson, O. Farish, T. Breckenridge, and B. M. Pryor, "Power transformer monitoring using UHF sensors: Installation and testing," in Conf. Record of the 2000 IEEE Int. Symp. on Elect. Insul. Anaheim, pp. 373-376
12 M. D. Judd and O. Farish, "FDTD simulation of UHF signals in GIS," in Proc. 10th Int. Symp. on High Voltage Engineering Montreal, vol. 6, Aug. 1997