Browse > Article

The Detection Characteristics of the Partial Discharge Pluses with Folded Dipole Type Sensors in the Oil Transformers  

Kim, Kwang-Hwa (한국전기연구원 산업전기연구단)
Yi, Sang-Hwa (한국전기연구원 산업전기연구단)
Sun, Jong-Ho (한국전기연구원 산업전기연구단)
Kang, Dong-Sik (한국전기연구원 산업전기연구단)
Kim, Jae-Chal (숭실대학교)
Publication Information
The Transactions of the Korean Institute of Electrical Engineers C / v.55, no.10, 2006 , pp. 485-491 More about this Journal
Abstract
This paper describes that the distribution of electromagnetic field occurred by PD(Partial Discharge) pulse was calculated with simulation program and characteristics of calibration and PD pulses measured with folded dipole types sensors were analyzed. As the distribution of electromagnetic field in simulation was very random the wide band measuring methods were good. Therefore three folded dipole antenna types sensors which had different their widths were designed and made. The signal according to direction and distance between sensor and pulse source in these sensor was measured and the spectrum of surface PD were acquired in the experiment of model transformer. In this result the characteristics of sensor which had middle width was better than others and the main spectrum of PD signals in surface discharge were existed in around 220MHz, 320MHz and from 450MHz to 750MHz.
Keywords
Oil-Immersed Transformer; Partial Discharge; Coupler;
Citations & Related Records
연도 인용수 순위
  • Reference
1 M.D. Judd, O.Farish, J,S Pearson, et al, 'Power Transformer monitoring using UHF Sensors insulation and Testing', Conference of 2000 IEEE Sym. On Electrical Insulation, 2000. pp. 373-376   DOI
2 Sang-Hwa Yi, Jong-Ho Sun, Kwang-Hwa Kim 'Development of PD Measurement Technology for Power Transformer (1)' 2005 Korea-Japan Joint Symp. on ED and HVE
3 F. Marangoni, J,P. Reynders, P.J, de Klerk, 'Investigation into the effects of different Antenna dimensions for UHF detection of partial discharge in power Transformers' 2003 IEEE Bologna Power Tech Conference, 2003 June pp23-26   DOI
4 Martin Judd, Gerry Cleary, 'Site Trial of UHF Partial Discharge Detection for Transformers,' Report on Diagnostic Tests Pof SG T4 at Neilston Substation, June 2001
5 Kwang-Hwa Kim, Jong-Ho Sun, Sang-Hwa Yi, Sang-Bo Han, Dong-Sik Kang, 'Development of On-line PD Measurement Technology for Power Transformer', International Conference on Condition Monitoring and Diagnosis, April 2006
6 CIGRE TFI5/33.03.05, 'Partial Discharge Detection System for GIS: Sensitivity Verification for the UHF Method and the Acoustic Method' Electra NO. 183, April 1999, pp75-87
7 Raja Kuppuswrany, 'On the UHF partial discharge measurement in transformer', 2003 Annual Report CEIDP pp349-352
8 'High-voltage test Techniques-Partial discharge measurements', IEC Pub. 60270, 2000
9 Christophe Moreau, Xavier Charpentier, 'On-Line Partial Discharge Detection System for Instrument Transformers', 1996 IEEE International Symposium on Electrical Insulation, June 1996, pp 65-68   DOI
10 Contantine A. Balanis, 'Antenna Theory (theory and design)', John WILEY & SONS, INC., second edition, 1982, pp. 458-462