Browse > Article

Evaluation Technique of Linearity of Ratio Error and Phase Angle Error of Voltage Transformer Comparison Measurement System Using Capacitor Burden  

Jung Jae Kap (한국표준과학연구원)
Kim Han Jun (한국표준과학연구원)
Kwon Sung Won (한국표준과학연구원)
Kim Myung Soo (한국표준과학연구원 전자기표준부)
Publication Information
The Transactions of the Korean Institute of Electrical Engineers C / v.54, no.6, 2005 , pp. 274-278 More about this Journal
Abstract
Voltage transformer(VT) comparison measurement system is usually used for measurements of ratio error and phase angle error of VT made in industry. Both ratio error and phase angle error in VT are critically influenced by values of burden of VT used. External burden effects on both ratio error and phase angle error in VT are theoretically calculated. From the theoretical calculation, a method of evaluation for linearity of ratio error and phase angle error in VT measurement system have been developed using the standard capacitive burdens, with negligible dissipation factor less than 10$^{-4}$. These burden consists of five standard capacitors, with nominal capacitance of 1.1 $\mu$F, 1 $\mu$F, 0.1 $\mu$F, 0.01 $\mu$F, 0.001 $\mu$F. The developed method has been applied in VT measurement system of industry, showing in good consistency and linearity within 0.001 $\%$ between theoretical and measured values.
Keywords
voltage Transformer; Ratio Correction Factor; Ratio Error; Phase Angle Error; Capacitive Burdens; Linearity;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 William E. Anderson 'A Calibration Service for Voltage Transfomers and High-Voltage Capacitors' NBS Measurement Services Special Publication 250-33, 1988
2 J. K. Das, 'Determination of Characteristics of a Three-Winding Potential Transformer and Predetermination of Errors' I. E. Journal-EL, 51, pp 51-58, 1970
3 D. A. Douglass, 'Potential Transformer Accuracy at 60 Hz Voltages above and below Rating and at Frequencies above 60 Hz' IEEE Trans. Power App, and Sys. PAS-100(3), pp 1370-1375, 1981   DOI   ScienceOn
4 정재갑, 권성원, 김규태, 김명수, '외부부담이 전압변성기의 비오차와 위상각오차에 미치는 영향에 대한 연구' 대한전기학회지, 53C, No. 3, pp. 137-142, 2004   과학기술학회마을
5 J. L. Settles, W. R. Farber, and E. E. Connor, 'The analytical and graphical determination of complete potential transformer characteristics' IEEE Trans. Power Apparatus and Systems, 79, No. 51, pp. 1213-1218, 1961