Characteristics of Leakage Current on Transmission Insulators Contaminated Artificially with Soluble and Nonsoluble Materials  

최인혁 (한전 전력연구원)
최장현 (한전 전력연구)
이동일 (한전 전력연구)
김찬영 (우석대학교 전기전자공학과)
Publication Information
The Transactions of the Korean Institute of Electrical Engineers C / v.53, no.9, 2004 , pp. 464-469 More about this Journal
Abstract
The leakage current of transmission insulators contaminated with salt, clay, and kaolin was examined in the Gochang's Long Periods Testing Center. The Insulators were artificially contaminated and estimated with the method of equivalent salt deposit density(ESDD). The artificially contaminated insulators were installed with the same condition as in the real transmission power line and applied with 154 (kV). The leakage current of the artificially contaminated insulators was measured with environment conditions, such as temperature and humidity by the a automatic leakage current detecting system. The leakage current of heavily contaminated insulator was abruptly increased above 72[%] of humidity, even though the leakage current was similar between the contaminated and non-contaminated insulators below 72[%] of humidity. Also, it was found that the humidity was much more important than the temperature in the leakage current of transmission insulators. The leakage current of contaminated insulator was decreased when it was plenty of rainfall, resulting from natural washing.
Keywords
Artificial Contamination; Porcelain Insulators; Leakage Current; ESDD;
Citations & Related Records
연도 인용수 순위
  • Reference
1 S. Grzybowski, R. A. Wilson, A. L. Libby, R. Barbre, 'Electrical and mechanical performance of porcelain suspension insulators removed from a 230kV transmission line after 35 years of service', IEEE proceedings, p.59, 1995   DOI
2 R. Matsuoka, H. Shinokubo, K. Kondo, Y. Mizuno, K. Naito, T. Fujimura, T. Terada, 'Assessment of basic contamination withstand voltage characteristics of polymer insulators', IEEE Transactions on power delivery, Vol. 11, No. 4, p. 1895, 1996   DOI   ScienceOn
3 I. H. Choi, et al, 'Characteristic Test on the leakage Current of Transmission Insulators', Proceeding of the KIEE Summer Annual Conference, Vol. A, p. 479, 2003
4 전영국외 6인, '전력설비의 염진해대책에 관한 연구(Ⅲ)', 한국전력공사 기술연구원 보고서, pp. 58-72, 1988
5 I. H. Choi, J. H. Choi, D. I. Lee, G. J. Jung, J. S. Ahn, '광대역 누설전류 자동측정 장치', Korea Patent 10-2003-0074891, 2003
6 G. H. Vaillancourt, J. P. Bellerive, M. St-Jean, C. Jean, 'New live line tester for porcelain suspension insulators on high voltage power lines', IEEE transactions on power delivery, Vol. 9, No. 1, p. 208, 1994   DOI   ScienceOn
7 F. F. Bologna, A. C. Britten, G. Watridge, D. J. Stevens, G. Grigorakis, 'Leakage current on lightly polluted on 275kV glass disc insulator strings in conditions of light wetting', IEEE proceedings, p. 739, 1999   DOI
8 Raji Sundararajan and Ravi Gorur, 'Influence of Inert Materials on the Pollution Flashover Voltage of Porcelain Insulators', Proceedings of IEEE Conference on Electical Insulation and Dielectric Phenomena(CEIDP' 94), 1994   DOI
9 심응보외 2인, '염진해 오손정도 및 기준정립에 관한 연구(최종보고서)', 한국전력공사 전력연구원, pp. 73-77, 2002