Browse > Article

Risk Assessment on Free Conducting Particle in GIS  

Yun, Jin-Yeol (KEPRI)
Park, Gi-Jun (KEPRI)
Gu, Seon-Geun (KEPRI)
Publication Information
The Transactions of the Korean Institute of Electrical Engineers C / v.51, no.4, 2002 , pp. 164-168 More about this Journal
Abstract
The main hazard leading to breakdown in GIS(Gas Insulated Switchgear) comes from free conducting particles, which can cross between tee electrodes and cause dielectric failure under the influence of the electric field. Bouncing height of the particle can be an important factor to evaluate the possibility of breakdown occurrence. In this paper, how to estimate, outside a GIS, the bouncing height of the particle was newly suggested when GIS is in service. Both experimental results using 362 kV test chamber and computer simulation results on estimating the height were presented and compared with each other.
Keywords
GIS; particle; bouncing height; risk assessment; breakdown;
Citations & Related Records
연도 인용수 순위
  • Reference
1 CIGRE Joint Working Group 33/23.12, 'Insulation co-ordination of GIS : return of experience, on site tests and diagnostic techniques', Electra No 176, pp. 67-97, Feb. 1998
2 Westinghouse Research and Development Center, 'Investigation of High-Voltage Particle-Initiated Breakdown in Gas-Insulated Systems,' EPRI Project 7835 Report., Pittsburgh, Pennsylvania, March, 1979
3 A G Sellars, O Farish and B F Hampton, 'Assessing the risk of failure due to particle contamination of : GIS using the UHF technique', IEEE Trans. on D&EI, Vol. 1, No. 2, pp. 323-331, 1994   DOI
4 박기준, 구선근, 윤진열, '362 kV GIS 내부 이물질 운동에 의한 UHF 부분방전 신호 검출', 2000년도 대한전기학회 추계 부문학술대회 논문집, p516-518, 2000
5 CIGRE Working Group 15.03, 'Diagnostic methods for GIS insulating systems', CIGRE session paper 15/23-01, 30, Aug.-5 Sept., 1992
6 윤진열, 박기준, 구선근, 한상옥, 'GIS 내 알루미늄 파티클의 거동에 따른 UHF 신호발생 특성', 2000년도 대한전기학회 추계 부문학술대회 논문집, p525-527, 2000
7 Risk assesment method and detection system of partial discharge generated inside of gas insulated high voltage switchgear and gas insulated gear, 특허출원
8 CIGRE Working Group 15.03, 'Partial discharge detection system for GIS : sensitivity verification for the UHF method and the acoustic method', ELECTRA No. 183, pp75-87, April 1999
9 U Schichler, J Gorablenkow and A Diessner, 'UHF PD detection in GIS substations during on-site testing', 8, DMMA, Edinburgh, UK., 2000