Browse > Article

Transport Capacity Design and Characteristics Evaluation of Al/Cu Composite Busbar for Power Equipments  

Bae, Joon-Han (한국전기연구원)
Kim, Hae-Joon (한국전기연구원)
Publication Information
The Transactions of the Korean Institute of Electrical Engineers B / v.55, no.12, 2006 , pp. 628-632 More about this Journal
Abstract
This paper deals with the electric and thermal characteristics of the composite busbar composed of aluminum and copper. When AC current is flowing in Cu busbar used widely in conservative equipments like power cable, transformer, and switchgear & controlgear most current is concentrated on the surface of the busbar by the skin effect. Therefore, if the Cu region in the busbar having low current density is replaced with aluminum, we can largely reduce the product cost and weight of the busbar. To conform the performance of the composite busbar, we designed and fabricated a test Al/Cu composite busbar. Maximun temperature rise of the busbar was $35^{\circ}C$ when 1600 Arms of AC current was applied to the test composite busbar($120mm{\times}10mm$). Based on test results, we can expect to make the low-priced and light power equipments using the Al/Cu composite busbar.
Keywords
Al/Cu composite busbar; skin effect; maximum temperature rise;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 KS D 5581
2 한전구매시방서 '변압기 단락강도 시험 규격'
3 '복합 경량 부스바 개발 및 가공기술 연구', 1차년도 최종보고서 과학기술처, 1997. 12
4 KS C 4507, 접속부 부스바 온도상승 시험법
5 R. W. Caven, Jr and J. Jalali, Predicting the contact resistance distribution of electrical contacts by modeling the contact interface, Proc. of the Thirty-seventh IEEE Holm Conf. Electrical Contacts, pp83-89, 1991   DOI
6 JEC - 2200
7 오연호 외, '부스바형 전기 접점의 단락통전 성능 해석 기법 개발', 대학전기학회논문지, 54B권, 1호, p27-32, 2005년, 1월   과학기술학회마을
8 Ragnar Holm, Electric Contacts : Theory and Applications 4th Ed., Berlin, Springer Verlag, pp1-26, 1979