Abstract
We estimated harmonics on power system of AC railway based on quantitatively measured harmonics and investigated the need of facilities for harmonics reduction. In order to analysis harmonics which inflow into power system due to increase in collector voltages and harmonic currents generated from the train when the railway is in operation, the railway system Is sectioned into power supply, railway line, AT, sectioning Post and subsectioning post. For analysis of extension of currents resulting from the railway loads, PWM converter, VVVF inverter and the feeder system are modeled based on the dynamic node technique(DNT). In order to test the usefulness of the DNT for analysis of harmonic effects, the measured harmonic currents and harmonic magnification ratios at the S/K substation are compared with simulation results using DNT modelling, which include the results for two cases with and without filters for suppression of harmonic currents. When 8 cars(4M4T) are in operation, the total sum of harmonic currents resulting from the train at M and T phases, which inflow into the substation along with the railway line, is calculated. Using the harmonics analysis program for railway feeder system with these data, the total harmonic distortion factor(710) at the outgoing point of KEPCO substation is computed. The calculation shows that when the maximum THD at the receiving point of H/K substation was 0.0443% which is much lower than 1.5% which is the allowable value of KEPCO at 154kV as well as IEEE-519 above 132kV This result indicates that any measure for harmonics reduction in Incheon International Airport Railway is not needed.
Keywords
AC railway; harmonics; power system; DNT; THD; harmonic magnification ratios;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 Giuseppe S. Buja, 'Optimum Output Waveforms in PWM Inverters', IEEE Trans. on IA, vol. IA-16, no. 6, pp. 830-836, 1980
2 D. Maischak, 'A novel control strategy for IGBT-Four-Quadrant converter', pp. 3179-3183, EPE'97
3 '구미제국의 고조파 억제대책의 상황', 月刊電機 通卷 第 95 號, pp. 46-50, 1996
4 '고조파 발생원에서의 대책', 月刊電機 通卷 第 86 號, pp. 31-39, 1995
5 Frank Flinders, 'Mixed electrical and mechanical simulations using dynamic systems analysis packages', the Proceeding of the 1993 IEEE/ASME joint railroad conference, 1993   DOI
6 한국철도기술공사, '충북선 조치원-봉양간 전철, 전력설비기 본설계보고서(변전설비)', 1997. 11
7 ROTEM, 'Incheon International Airport Railway Link Project', Feb., 2001
8 '배전계통 고조파 장해 방지대책', 電氣協同硏究會, 第 37 卷, 第 3號, pp. 1-184, 1981
9 철도기술연구원, '철도급전시스템 고조파 해석 프로그램', 2002. 2