Browse > Article

Design and Fabrication of Light-Weight Composit Bus Bar  

Bae Joon-Han (한국전기연구원 초전도 응용연구그룹)
Bea Duck-Kweon (한국기계연구원 기계시스템신뢰성연구센터)
Publication Information
The Transactions of the Korean Institute of Electrical Engineers A / v.55, no.8, 2006 , pp. 334-340 More about this Journal
Abstract
Copper is widely used in electric wire, cable, conductor in electric devices. As the demand for electric power is increasing rapidly, electric power devices are getting amazingly bigger and complicated. The using of light-weight conductor can reduce the size and making cost of the electric devices. In high-frequency application, Electric current in a conductor tends to shift to the surface of the conductor, resulting in an uneven current distribution in the inner conductor. In the extreme case the current may essentially concentrate in the 'skin' of the inner conductor as a surface current. In high frequency application, therefore, inner area of copper conductor may replace with aluminum conductor, which reduces the weight of conductor. This paper describes the manufacture and evaluation of composite conductors made of copper and aluminum. The optimum extruding ratio was 16 at $300^{\circ}C$. The electrical resistance of manufactured composite bus bar was $57{\mu}{\Omega}$ at DC and $49.5{\mu}\{Omega}$ at 300Hz.
Keywords
Copper; Aluminum Solenoids; Composite Bus Bar; Skin; Surface Current;
Citations & Related Records
연도 인용수 순위
  • Reference
1 David K. Cheng, Field and Wave Electromagnetics, Addison-Wesley Publishing Company, pp. 370, 1989
2 http://www.bussmann.com/library /docs/Disconnect/1200A3150 Anfds.pdf
3 http://www.eatonelectric.com.au/brochures/SVS_08. pdf