Browse > Article

A Study on the Susceptibility of Single-phase Sensitive Loads and the Three-phase Induction Motor by Voltage Sag  

Yun Sang-Yun (LS산전 전력연구소)
Moon Jong-Fil (기초전력연구원 전력시스템연구실)
Kim Jae-Chul (숭실대 공대 전기공학부)
Lee Hee-Tae (숭실대 공대 전기공학부)
Publication Information
The Transactions of the Korean Institute of Electrical Engineers A / v.55, no.1, 2006 , pp. 37-44 More about this Journal
Abstract
In this paper we explore the susceptibility of common sensitive loads by voltage sags of power distribution systems. The experimental approach was used for obtaining the susceptibility of single-phase loads and the three-phase induction motor. The experimental result of single-phase loads was transformed to the ITIC(Information of Technology Industry Council) format and used for evaluating the adverse impacts of a individual and repetitive sags using the performance contour of the foreign standard data. In order to assess the impact of voltage sags on three-phase induction motor, also, the experiment was peformed. The experiment was focused on the current, torque, and speed loss of the motor during a voltage sag. For comparing the impacts of individual and repetitive voltage sags, the variations of motor torque is focused among the experimental results. The sensitive curves of instantaneous current peak are used to describe the susceptibility of three-phase induction motor and 진so it were used for the quantitative analysis of the impact of three-phase induction motor due to voltage sags. Through the results of experiment, we verified that some types loads have more severe impact at repetitive voltage sags than individual ones and proposed method can be effectively used to evaluate the actual impact of voltage sags.
Keywords
Repetitive Voltage Sags; Susceptibility; Sensitive Loads; Three-phase Induction Motor;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 C. Becker et al., 'Proposed chapter 9 for predicting voltage sags (dip) in revision to IEEE Std 493, the Gold Book,' IEEE Trans. on Ind. Appl., vol. 30, no .3, pp. 805-821, May/Jun. 1994   DOI   ScienceOn
2 Y. Sekine, T. Yamamoto, S. Mori, N. Saito, and H. Kurokawa, 'Present state momentary voltage dip interferences and the countermeasures in Japan,' Int. Conf. on Large Electric Networks (CIGRE), 34th Session, Sep. 1992
3 Electromagnetic compatibility (EMC), Part 2: Environment, Section 2: Voltage dips,short interruptions and statistical measurement results, IEC61000-2-8
4 IEEE recommended practice for monitoring electric power quality, IEEE Std. 1159,1995
5 Math H. J. Bollen, Understanding power Quality problems-voltage sags and interruptions, New York: IEEE Press, 2000
6 IEEE guide for service to equipment sensitive to momentary voltage disturbances, IEEE Std. 1250,1995
7 J. C. Das, 'Effects of momentary voltage dips on the operation of induction and synchronous motors', IEEE Trans. on Ind. Appl., vol. 26, no. 4, July/August, 1990   DOI   ScienceOn
8 J. F. Moon, J. C. Kim, S. Y. Yun, B. S. Kang, 'Quantitative Evaluation of the Impact of Low-Voltage Loads Due to the Successive Voltage Sags', Trans. on KIEE, vol. 53A, no. 12, Dec. 2004   과학기술학회마을
9 IEEE recommended practice for evaluating electric power system compatibility with electronic process equipment, IEEE Std. 1346, 1998
10 L. Guasch, F. Corcoles, J. Pedra, 'Effects of symmetrical and unsymmetrical voltage sags on induction machines', IEEE Trans. on PWRD, vol. 19, no. 2, Apr. 2004   DOI   ScienceOn
11 G.-J Lee, M. M. Albu, G. T. Heydt, 'A power Quality index based on equipment sensitive, cost, and network vulnerability', IEEE Trans. on PWRD, vol. 19, no. 3, pp. 1504-1510, Jul. 2004   DOI   ScienceOn
12 J. Lamoree, D. Mueller, P. Vinett, W. Jones, and M. Samotyj, 'Voltage sag analysis case studies,' IEEE Trans. on Ind. Appl., vol. 30, no. 4, pp. 1083-1089, Jul./Aug. 1994   DOI   ScienceOn
13 J. C. Gomez, M. M. Morcos, C. A. Reineri, and G. N. Campetelli, 'Behavior of induction motor due to voltage sags and short interruptions,' IEEE Trans. on PWRD, vol. 17, no. 2, Apr. 2002   DOI   ScienceOn
14 R. C. Dugan, D. L. Brooks, M. Waclawiak, and A. Sundaram, 'Indices for assessing utility distribution system RMS variation performance,' IEEE Trans. on PWRD, vol. 13, no. 1, pp. 254-259, Jan. 1998   DOI   ScienceOn
15 L. E. Conrad and Math H. J. Bollen, 'Voltage sag coordination for reliable plant operation,' IEEE Trans. on Ind. Appl., vol. 33, no. 6, pp. 1459-1464, Nov./Dec. 1997   DOI   ScienceOn