Browse > Article

Development of Ground Fault Protective Relaying Schemes for DC Traction Power Supply System  

Chung Sang-Gi (한국철도기술연구원)
Jeong Rag-Gyo (한국철도기술연구원)
Cho Hong-Sik (한국철도기술연구원)
Lee Ahn-Ho (한국철도기술연구원)
Kwon Sam-Young (한국철도기술연구원)
Publication Information
The Transactions of the Korean Institute of Electrical Engineers A / v.54, no.9, 2005 , pp. 427-433 More about this Journal
Abstract
In DC tracking power supply system, ground faults are currently detected by the potential relay, 64P. Though 64P relay detects ground fault, it cannot Identify the faulted region which causes long traffic delays and safety problem to passengers. Two new ground fault protective relay schemes that can identify the faulted region are presented in this paper. One is bus differential protective relay and the other is ground overcurrent protective relay. Both type of relays is similar in principle to the ordinary bus differential protective relay and the ground overcurrent relay used in other power system. In DC traction power supply system, since it is ungrounded, ground fault current is not big enough to operate those relays. To solve the problem, a current control device, called device 'X', is newly introduced in both system, which enables large amount of ground fault current flow upon the positive line to ground fault. Algorithms for these relays are developed and their validity are verified by EMTP simulation.
Keywords
DC급전;보호계전;지락보호;도시철도;지락사고;전력공급시스템;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 일본철도전화협회, 급전회로보호시스템, P9
2 서울도시철도공사, '전기(변전)분야실습교재', pp153-156, 1998