Browse > Article

A Study on the Out-of-Step Detection Algorithm using Time Variation of Complex Power-Part I : The Variation of Complex Power Trajectory in Complex Plane  

Kwon O-Sang (성균관대 대학원 차세대전력기술연구센터)
Kim Chul-Hwan (성균관대 정보통신공학부 차세대전력기술연구센터)
Publication Information
The Transactions of the Korean Institute of Electrical Engineers A / v.54, no.7, 2005 , pp. 345-351 More about this Journal
Abstract
An out-of-step condition results from the loss of the synchronism of the generators. A disturbance in a power system causes the generator angle to oscillate. When there is a severe disturbance such as a heavy current fault loss of major generation or loss of a large block of load, the oscillation can be severe and even increase largely and finally the out-of-step condition may un. During the power swing and out-of-step conditions, the apparent impedance at a relay location changes, and the power flow also changes as the angle difference is varied. This paper presents a method to analyze the trajectory of complex power during a power swing and out-of-step condition. The trajectory of the complex power is analyzed when a power swings and a fault occurs. Moreover, the complex power is analyzed when the ratios between the voltages at both sides and the line impedances are changed. These methods are verified through simulation using the ATP/EMTP MODELS.
Keywords
Out-of-step; Power Swing; Power System; Complex Power; EMTP;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 Chul-Hwan Kim, Hyun Kim, Young-Hun Ko, Sung-Hyun Byun, R. K. Aggarwal, A. T. Johns, 'A Novel Fault-detection Technique of High-Impedance Arcing Faults in Transmission Lines using the Wavelet Transform', IEEE Trans. on Power Delivery, vol. 17,no. 4, pp. 921-929,Oct. 2002   DOI   ScienceOn
2 C. H. Kim, J. Y. Heo, R. K. Aggarwal, 'An Enhanced Zone 3 Algorithm of a Distance Relay using Transient Components and State Diagram', IEEE Tran. on Power Delivery, vol. 20, no. 1, pp. 39-46, Jan. 2005   DOI
3 Sang-Pi! Ahn, Chul-Hwan Kim, R. K Aggarwal, A. T. Johns, 'An Alternative Approach to Adaptive Single Pole Auto-reclosing in High Voltage Transmission Systems based on Variable Dead Time Control', IEEE Tran. on Power Delivery, vol. 16,no. 4,pp. 676-686, Oct. 2001   DOI   ScienceOn
4 Chul-Hwan Kim, Myung-Hee Lee, R. K. Aggarwal, A. T. Johns, 'Educational Use of EMTP MODELS for the Study of a Distance Relaying Algorithm for Protecting Transmission Lines', IEEE Trans. on Power Systems, vol. 15,no. 1, pp. 9-15, Feb. 2000   DOI   ScienceOn
5 J.Y. Heo, C.H. Kim, R.K. Aggarwal, 'Simulation of the Distance Relay using EMTP MODELS', KIEE International Transactions on Power Engineering, vol. 4-A, no. 1, pp. 26-32, Mar. 2004   과학기술학회마을
6 Jan Machowski, Janusz W. Bialek, James R. Bumby, Power System Dynamics and Stability, John Wiley & Sons inc.,1998, pp.215-234
7 V. Van Acker, et al, 'System Protection Schemes in Power Networks', CIGRE SCTF 38.02.19, 2000
8 P. M. Anderson, Power System Protection, IEEE Press, 1997, pp. 853-905
9 V. Centeno, A. G. Phadke, A. Edris, J. Benton, M. Gaudi, G. Michel, 'An Adaptive Out-of-Step Relay', IEEE Trans. Power Delivery, vol. 12, No.1, pp. 61-71, Jan. 1997   DOI   ScienceOn
10 Demetrios Tziouvaras, 'Power System Stability and Relaying', IEEE PSRC Meeting, Jan. 2003
11 IEEE PSRC Working Group C-6, 'Wide Area Protection and Emergency Control', IEEE PES Power System Relaying Committee, 2002