Browse > Article
http://dx.doi.org/10.3795/KSME-B.2004.28.2.167

A Study on the Development of Fouling Analysis Technique for Shell-and-Tube Heat Exchangers  

Hwang, Kyeong-Mo (한전기술(주) 재료기술연구그룹)
Jin, Tae-Eun (한전기술(주) 재료기술연구그룹)
Publication Information
Transactions of the Korean Society of Mechanical Engineers B / v.28, no.2, 2004 , pp. 167-173 More about this Journal
Abstract
Fouling of heat exchangers is generated by water-borne deposits, commonly known as foulants including particulate matter from the air, migrated corrosion produces; silt, clays, and sand suspended in water; organic contaminants; and boron based deposits in plants. The fouling is known to interfere with normal flow characteristics and reduce thermal efficiencies of heat exchangers. This paper describes the fouling analysis technique developed in this study which can analyze the thermal performance for heat exchangers and estimate the future fouling variations. To develop the fouling analysis technique fur heat exchangers, fouling factor was introduced based on the ASME O&M codes and TEMA standards. For the purpose or verifying the fouling analysis technique, the routing analyses were performed for four heat exchangers in several nuclear power plants; two residual heat removal heat exchangers of the residual heat removal system and two component cooling water heat exchangers of the component cooling water system.
Keywords
Fouling Factor; Residual Heat Removal Heat Exchanger; Component Cooling Water Heat Exchanger; Overall Heat Transfer Coefficient;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 Ha, M. Y., Lee, D. R., Ahn, S. P., and Park H. D., 1998, 'An Experimental Study on Fouling over a Single Tube,' KSME International Journal, Vol. 12, No. 6, pp. 1162-1173   DOI
2 Perry, R. H., Chemical Engineer's Handbook, Sixth Edition, McGraw Hill, pp. 10. 24-10. 31
3 TEMA, 1988, Standards of the Tubular Exchanger Manufactures Association, 7th Edition, pp. 101-104
4 ASME, 1994, Standards and Guides for Operation and Maintenance of Nuclear Power Plants, ASME OM-S/G-Part 2
5 EPRI, 1991, Heat Exchanger Performance Monitoring Guidelines, NP-7552
6 Conklin, J. E., 1995, Aging Management Evaluation for Heat Exchangers, WCAP-14341, Westinghouse Owner's Group
7 Kim, N. H., Lee, Y. P., and Yoon, S. Y., 1995, 'A Study on the Pressure Loss, Heat Transfer Performance, and Fouling Control in Liquid Fluidized Bed Heat Exchangers,' Energy Engg. Journal, Vol. 4, pp. 59-66   과학기술학회마을
8 Kim, M. S. and Ota Terukazu, 1997, 'Fouling Effect of Geothermal Water Scale on Heat Transfer Around a Tube in a Bank,' KSME International Journal, Vol. 11, pp. 705-713   DOI