Due to climate change coupled with the increase of zoonotic diseases, infectious diseases are more likely to occur and spread in the future; therefore, new alternatives and methods related to treatment environments should be considered. Under the global landscape of the prolonged COVID-19 pandemic, the number of patients who need to be cared for through negative isolation rooms is increasing. Consequently, it is essential to secure temporary medical facilities that can remain operational during a pandemic. These facilities must be safe and secured so that public confidence is increased, and treatment expedited. This study proposes a reference model and HVAC design criteria for mobile negative pressure isolation room modular systems to minimize cross-infection inside the health care space and ensure the safety of health care workers (HCWs) as well as securing rapid medical service supplies. The mobile negative pressure isolation room module basically reflects the one-way airflow direction from clean zone to dirty zone, and appropriate differential pressure control that separates the air environment between the HCW's and the patient. If properly installed, the location of the exhaust air vents need to be directly above the patient's bed, specifically on the wall near the head of the bed. The installation of the headboard on the patient's bed as an exhaust air ventilation location was considered for infection prevention and control when performing aerosol-generating procedures (AGPs).
Keywords
Infectious disease; Mobile negative pressure isolation room; Cross-infection prevention; Design criteria; HVAC considerations;
Citations & Related Records
연도 인용수 순위
  • Reference
1 CDC. (2021). Scientific brief: SARS-CoV-2 transmission, Centers for Disease Control and Prevention (Updated May 7, 2021).
2 Cho, J., Woo, K., & Kang, H. (2017). Experimental study of an AIIR ventilation system for effective removal of airborne contamination in hospitals, Journal of the Architectural Institute of Korea Structure & Construction, 33(3), 85-90.   DOI
3 Suvanjan, B., Kunal, D., Akshoy, R.P., & Ranjib, B. (2020). A novel CFD analysis to minimize the spread of COVID-19 virus in hospital isolation room, Chaos, Solitons & Fractals, 139, 110294.   DOI
4 Tran, K., Cimon, K., Severn, M., Pessoa-Silva, C.L., & Conly, J. (2012). Aerosol generating procedures and risk of transmission of acute respiratory infections to healthcare workers: a systematic review, PLoS One, 7(4), e35797.   DOI
5 WHO. (2020). COVID-19 Virtual press conference, The World Health Organization (July 7, 2020).
6 Jo, S.M., Kim, G.H., & Sung, M.K. (2017). Analysis on contaminant migration from negative pressure isolation ward during door opening and human movement using CFD simulation, Journal of the Architectural Institute of Korea Structure & Construction, 33(10), 61-68.   DOI
7 Jung, M., & Hong, J.K. (2019). A numerical study on cough particle dispersion and deposition according to the location of exhaust air diffuser in airborne infection isolation room, Korean Journal of Air-Conditioning and Refrigeration Engineering, 31(12), 559-567.   DOI
8 Hick, J.L., Barbera, J.A., & Kelen, G.D. (2009). Refining surge capacity: conventional, contingency, and crisis capacity. Disaster Medicine and Public Health Preparedness, 3(1), 59-67.
9 Hick, J.L., Christian, M.D., & Sprung, C.L. (2010). Chapter 2. Surge capacity and infrastructure considerations for mass critical care. Intensive Care Medicine, 36(1), 11-20   DOI
10 Cho, J., Woo, K., & Kim, B.S. (2018). Removal of airborne contamination in airborne infectious isolation rooms, ASHRAE Journal, 61(2), 8-21.
11 Lee, B., Yoon, J., Yoon, C., Lee, K., Min, K.B., Yeo, M.S., & Kim, K-W. (2017). Comparative analysis of domestic and foreign guidelines for airborne infection isolation rooms (AIIRs), Journal of Korean Institute of Architectural Sustainable Environment and Building Systems, 11(3), 230-237.
12 Lee, S., & Lee, J.W. (2017). A Design methodology for the temporary isolation room based on the MERS-Cov infection control guideline - In case of temporary negative pressure isolation room using shipping container, Journal of the Architectural Institute of Korea Planning & Design, 33(12), 19-28.   DOI
13 Asad, H., Johnston, C., Blyth, I., Holborow, A., Bone, A., Porter, L., Tidswell, P., & Healy, B. (2020). Health care workers and patients as trojan horses: a COVID19 ward outbreak, Infection Prevention in Practice, 2(3), 100073.   DOI
14 KADC. (2019). Operation and management guidelines for nationally-designated inpatient beds, Korea Disease Control and Prevention Agency / The Ministry of Health and Welfare.
15 Kim, D.G., & Nam, T.J. (2021). COVID-19 management in medical facilities - mobile negative pressure module system, Air Cleaning Technology, 34(2), 46-61.
16 Kim, J., & Hong, J.K. (2018). A Numerical study on pressure fluctuation and air exchange volume of door opening and closing speeds in negative pressure isolation room, Journal of The Korea Institute of Healthcare Architecture, 24(1), 51-58.   DOI
17 Kwon, S., & Sung, M. (2016). Isolation effectiveness by progressive space organization in negative pressured isolation unit, Journal of The Korea Institute of Healthcare Architecture, 22(4), 79-86.   DOI
18 Lurie, N., Dausey, D.J., Knighton, T., Moore, M., Zakowski, S., & Deyton, L. (2008). Community planning for pandemic influenza: lessons from the VA health care system, Disaster Medicine and Public Health Preparedness, 2(4), 251-257.   DOI
19 REHVA. (2020). REHVA COVID-19 guidance document; How to operate HVAC and other building service systems to prevent the spread of the coronavirus (SARS-CoV-2) disease (COVID-19) in workplaces, the Federation of European Heating, Ventilation and Air Conditioning Associations.
20 Mead, K., Feng, A., Hammond, D., & Shulman, S. (2012). Expedient methods for surge airborne isolation within healthcare settings during response to a natural or manmade epidemic, Department of Health and Human Services, Centers for Disease Control and Prevention, National Institute for Occupational Safety and Health, EPHB Report No. 301-05f
21 CDC. (2020a). Clinical questions about COVID-19: questions and answers, Centers for Disease Control and Prevention (Updated December 4, 2020).
22 Peavey, E., Kim, M., Roark, J. Holton, S., Schroer, J., Scrantom, B. Evans, J. Beebe, C., & Flannery, J. (2021). The pandemic-resilient hospital: How design can help facilities stay operational and safe, HKS, Arup and the American Society for Health Care Engineering.
23 Miller, S.L., Clements, N., Elliott, S.A., Subhash, S.S., Eagan, A., & Radonovich, L.J. (2017). Implementing a negative -pressure isolation ward for a surge in airborne infectious patients, American Journal of Infection Control, 45(6), 652-659.   DOI
24 OSHA. (2021). Protecting Workers: guidance on mitigating and preventing the spread of COVID-19 in the Workplace, Occupational Safety and Health Administration (Updated August 13, 2021).
25 ASHRAE. (2019). ANSI/ASHRAE Standard 62.1-2019: Ventilation for acceptable indoor air quality, American Society of Heating, Refrigerating and Air-conditioning Engineers.
26 ASHRAE/ASHE. (2017). ANSI/ASHRAE/ASHE Standard 170-2017: Ventilation of health care facilities, American Society of Heating, Refrigerating and Air-conditioning Engineers / the American Society for Health Care Engineering.
27 CDC. (2003). Guidelines for environmental infection control in health-care facilities, Centers for Disease Control and Prevention.
28 CDC. (2020b). Interim infection prevention and control recommendations for healthcare personnel during the coronavirus disease 2019 (COVID-19) Pandemic, Centers for Disease Control and Prevention (Updated November 4, 2020).