Browse > Article
http://dx.doi.org/10.9714/psac.2013.15.4.034

Characteristics of the SFCL by turn-ratio of three-phase transformer  

Jeong, I.S. (Chosun University)
Choi, H.S. (Chosun University)
Jung, B.I. (Chosun University)
Publication Information
Progress in Superconductivity and Cryogenics / v.15, no.4, 2013 , pp. 34-38 More about this Journal
Abstract
According to the increase of electric consumption nowadays, power system becomes complicated. Due to this, the size of single line-to-ground fault from power system also increases to have many problems. In order to resolve these problems effectively, an Superconducting Fault Current Limiter(SFCL) was proposed and continuous study has been done. In this paper, an SFCL was combined to the neutral line of a transformer. An superconductivity has the characteristics of zero resistance below critical temperature. because of this, SFCL has nearly zero resistance. so we connecting SFCL to neutral line will not only have any loss in the normal operation but also have the less burden of electric power because of only limiting the initial fault current. We analyzed the characteristics of current, voltage according to the changes of turn ratio of 3 phase system in case of combinations of an SFCL to the neutral line. It was confirmed that the limiting rate of initial fault current by the increase of turn ratio was reduced.
Keywords
SFCL; Turn-ratio; Current limitation; Line-to-ground;
Citations & Related Records
Times Cited By KSCI : 2  (Citation Analysis)
연도 인용수 순위
1 H. S. Choi, O. B. Hyun, H. R. Kim, K. B. Park, "Switching properties of hybrid type superconducting fault current limiter using YBCO stripes" IEEE Trans. Appl. Superconduct, vol. 12, pp. 1833 -1838, 2002.   DOI   ScienceOn
2 J. S. Kim, S. H. Lim, J. C. Kim, "Comparative Analysis on Current Limiting Characteristics of Hybrid Superconducting Fault Current Limiters (SFCL) with First Half Cycle Limiting and Non-Limiting Operations," JEET. vol. 7, no. 5, pp. 653-806, 2012.
3 Yong-Sun Cho, Hyo-Sang Choi, Sung-Pil Go,"Operational Characteristics of Transformer-Type SFCL with or without Neutral Line between the Secondary windings and Superconducting units", Trans. KIEE. Vol. 60, No. 6, pp. 1268-1273, 2011.   과학기술학회마을   DOI   ScienceOn
4 R. Kreutz, J. Bock, F. Breuer, K. P. Juengst, M. Kleimaier, H.-U. Klein, D. Krischel, M. Noe, R. Steingass, and K. H. Weck, "System technology and test of curl 10, a 10 kV, 10 MVA resistive high-Tc superconducting fault current limiter," IEEE Trans. on Appl. Superconduct., vol. 15, pp. 1961-1964, 2005.   DOI   ScienceOn
5 M.H.Kim, J.S.Kim, I.K.You, S.H.Lim, J.C.Kim, "A study on Practical Impedance of Superconducting Fault Current Limiter on Bus Tie in a Power Distribution System", JEET, vol.1, no.1, pp. 1-122, 2011.
6 A. C. Lapthorn, I. Chew, W. G. enright, and P. S. Bodger, "HTS transformer: construction details, test results, and noted failure mechanisms", IEEE Trans. Power Delivery, vol. 26, no.1, 394-399, 2011.   DOI   ScienceOn
7 B. W. Lee, K. B. Park, J. Sim, I. S. Oh, H. G. Lee, H. R. Kim, O. B. Hyun, "Design and Experiments of Novel Hybrid Type Superconducting Fault Current Limiters," IEEE Trans. Appl. Supercond., vol. 18, no. 2, pp. 624-627, 2008.   DOI   ScienceOn
8 Y. Yorozu, M. Hirano, K. Oka, and Y. Tagawa, "Electron spectroscopy studies on magneto-optical media and plastic substrate interface," IEEE Transl. J. Magn. Jpn., vol. 2, pp. 740-741, 1987 [Dig. 9th Annual Conf. Magn. Jpn., pp. 301, 1982].   DOI   ScienceOn
9 M. Young, The Technical Writer's Handbook, Mill Valley, CA: University Science, 1989.