Browse > Article
http://dx.doi.org/10.9714/psac.2010.12.1.022

Analysis of Bus Voltage Sag Caused by Recloser-Fuse Coordination in a Power Distribution System with SFCL  

Kim, Myoung-Hoo (숭실대 공대 전기공학부)
Kim, Jin-Seok (숭실대 공대 전기공학부)
You, Il-Kyoung (숭실대 공대 전기공학부)
Wang, Soon-Wook (숭실대 공대 전기공학부)
Moon, Jong-Fil (충주대 첨단산업대 전기공학과)
Lim, Sung-Hun (숭실대 공대 전기공학부)
Kim, Jae-Chul (숭실대 공대 전기공학부)
Publication Information
Progress in Superconductivity and Cryogenics / v.12, no.1, 2010 , pp. 22-27 More about this Journal
Abstract
This paper analyzed bus voltage sag caused by recloser-fuse coordination in a power distribution system with SFCL. Generally, the recloser is installed to upstream of fuse to clear against both permanent and temporary faults appropriately, when the fault happened and to block expansion of the fault area. Furthermore, when the fault occurred, bus voltage sag is caused by increased fault currents. However, in a power distribution system with SFCL, the fault current could be decreased by the effect of the impedance value of the SFCL and place to install one as long as it could improve bus voltage sag. Therefore, to analyze the effect of the improvement of bus voltage sag caused by recloser-fuse coordination in a power distribution system with SFCL, we used PSCAD/EMTDC about a permanent fault at the place behind the fuse.
Keywords
Recloser-Fuse coordination; voltage sag; power distribution system; superconducting fault current limiter;
Citations & Related Records
Times Cited By KSCI : 4  (Citation Analysis)
Times Cited By SCOPUS : 0
연도 인용수 순위
1 김준환, 이강완, "전력계통, 고장전류 증대와 대응방안", 전기저널, pp. 19-31, 1998.
2 이희태, 문종필, 설규환, 윤상윤, 김재철, "영구정전과 순간전압강하를 고려한 신뢰도 비용 평가" 한국조명.전기설비학회논문지, vol. 22, no. 5, pp. 13-20, 2008.
3 한국전력공사, "배전보호기술서", 1995.
4 김진석, 임성훈, 문종필, 김재철, 현옥배, "MTR 성점 접지에 초전도 전류제한기 적용시 지락과 전류계전기 동작 분석", 대한전기학회, vol. 58, no. 11, pp. 2089-2094, 2008.
5 W. Paul and M. chen, "Superconductiong control for surge currents", IEEE Spectrum, vol. 35, pp. 49-54, 1998.
6 Cooper Industries, "Electrical distribution-System Protection 3rd ed.", Cooper Power System, 1990.
7 B. W. Lee, J. Sim, K. B. Park, I. S.Oh, S. W. Yim, H. R. Kim, O. B. Hyun, "Fabrication and Testa o f the 24kV class Hybrid Superconduction Fault Current Limiter", Journal of the Korea Instisute of Applied Superconductivity and Cryogenics, vol. 9, no. 4, 32-36, 2007.
8 한전표준규격, "Fuse links for cut out switch", 2006.
9 임성정, 김재철, "배전시스템에서의 재폐로에 의한수용가측 영향의 정량적 평가", 한국조명.전기설비학회논문지, vol. 12, no. 2, pp. 7-14, 1998.
10 김명후, 김진석, 유일경, 문종필, 임성훈, 김재철, "배전계통에 초전도한류기 적용기 Recolser-Fuse 협조 방법", 2009년도 대한전기학회 하계학술대회 논문집, pp. 8-9, 2009.
11 김명후, 김진석, 유일경, 문종필, 임성훈, 김재철, "배전계통에 초전도전류제한기 적용시 Recloser-Fuse 협조 방법에 관한 연구", 대한전기학회, vol. 58, no. 10, 1835-1841, 2009.
12 안재민, 김진석, 문종필, 임성훈, 김재철, 김철환, 현옥배, "배전계통에 초전도 전류 제한기 적용시 보호 협조 분석", 대한전기학회, vol. 57, no. 5, pp. 755-760, 2008.
13 문종필, 임성훈, 김재철, 김진석, 김명후, 유일경, "배전계통에 초전도한류기 적용시 전압 Sag 분석", 2009년도 대한전기학회 하계학술대회 논문집, pp. 262-263, 2009.