Abstract
Since the discovery of the high temperature superconductors many researches have been performed for the practical applications of superconductivity technologies in various fields. As results, significant progress has been achieved. Especially, Superconducting Fault Current Limiter (SFCL) offers an attractive means In limit fault current in power systems. HTS resistive type SFCL is based on the ultra fast transition from the superconducting (non resistive) state to the normal (resistive) state by overstepping the critical current density, In this study, the simulation method of resistive type superconducting fault current limiter using EMTDC is proposed and the developed EMTDC model of SFCL is applied to the modeled power network using the Parameters of real system.